Valor Ventana 1200EAN Installation & Owner's Manual page 25

Direct vent zc fireplace
Table of Contents

Advertisement

Rules
1. Any hearth/fl oor in front of fi replace within 4 inches of the bottom of the unit must be non-combustible and
project a minimum distance as shown on page 26. The hearth/fl oor must have a non-combustible fi nish applied
over the 1/2 inch insulation board provided with the engine. This insulation board acts as a thermal break.
2. Minimum hearth projection is determined by a combination of the height of the hearth above the surface of
combustible fl oor or carpet and the distance between the hearth and the bottom of the fi replace.
3. Combustible baseboards (1 inch thick or less) located on the wall are acceptable provided they are located
below the base of the raised fi replace.
Unit Raised Above Combustible Hearth or Floor
4" MIN.
Combustible
Floor
Hearth Requirements
Base of Fireplace
Face of
Cement
Board
When the appliance is installed directly on
Top Face of
carpeting, tile or other combustible material
Combustible
other than wood fl ooring, the appliance
Floor or
shall be installed on a metal or wood panel
Carpet
extending the full width and depth of the
appliance
QUALIFIED
INSTALLER
25