Emission
The following standards are met for cable lengths up to 100m.
Table 8-6 FXMP25 emission compliance
Schaffner FN3280H-25-33
Filters can be sourced directly from Schaffner.
Key (shown in decreasing order of permitted emission level):
C4
EN 61800-3:2004 second environment, restricted distribution (Additional
measures may be required to prevent interference).
C2
Industrial generic standard EN 61000-6-4:2007.
EN 61800-3:2004 first environment restricted distribution (The following caution
is required by EN 61800-3:2004).
This is a product of the restricted distribution class according to IEC 61800-3. In a
residential environment this product may cause radio interference in which case the
user may be required to take adequate measures.
CAUTION
EN 61800-3:2004 defines the following:
The first environment is one that includes residential premises. It also includes
establishments directly connected without intermediate transformers to a low-
voltage power supply network which supplies buildings used for residential
purposes.
The second environment is one that includes all establishments other than those
directly connected to a low-voltage power supply network which supplies buildings
used for residential purposes.
Restricted distribution is defined as a mode of sales distribution in which the
manufacturer restricts the supply of equipment to suppliers, customers or users who
separately or jointly have technical competence in the EMC requirements of the
application of drives.
FXMP25 User Guide
Issue Number: 3
Filter
No filter
www.controltechniques.com
Conformity
C4
C2
59