Emerson FXMP25 User Manual page 37

Field controller
Table of Contents

Advertisement

59
Coding
Range
Default
Update rate
The programmable value of the armature back emf or armature voltage (standalone
mode), in volts, at which the field begins to weaken. Defined as the voltage at which
base speed is reached.
60
Coding
Range
Update rate
The calculated voltage being generated on the field output terminals. Calculated from
applied mains voltage and firing angle.
62
Coding
Range
Default
Update rate
Gains used during field weakening. Setting these too high could cause instability during
field weakening.
63
Coding
Range
Default
Update rate
Gains used during field weakening. Setting these too high could cause instability during
field weakening.
64
Coding
Range
Default
Update rate
When this parameter is set to OFF (0) the field controller operates with the field
weakening voltage loop. When set to On (1) the flux level is determined by reference on
terminal 3.
FXMP25 User Guide
Issue Number: 3
Field weakening voltage set point
Bit
FI
Txt
0 to 750 V
Eur: 400, USA: 480
Background write
Field output voltage
Bit
FI
Txt
1
0 to 500 V
Background write
Field weakening loop P gain
Bit
FI
Txt
0.00 to 99.99
0.40
Background read
Field weakening loop I gain
Bit
FI
Txt
0.00 to 99.99
5.00
Background read
External flux reference select
Bit
FI
Txt
OFF (0) to On (1)
OFF (0)
Background read
www.controltechniques.com
VM
DP
ND
US
VM
DP
ND
US
1
VM
DP
ND
US
2
VM
DP
ND
US
2
VM
DP
ND
US
RW
BU
PS
1
1
1
RW
BU
PS
RW
BU
PS
1
1
1
RW
BU
PS
1
1
1
RW
BU
PS
1
1
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents