Table 7-3 Quick start commissioning / start up from defaults for Mentor II mode
Action
Ensure:
•
•
Before power up
•
Ensure:
Power up the field
•
controller
•
Setting up the field
•
current feedback
scaling
To select Mentor II mode
•
Select Mentor II
•
mode
•
•
The Mentor II has taken control of the FXMP25. Setting up
Setting up the field
should now be carried out using the Mentor II. Please refer to the
controller
Mentor II User Guide Menu 6.
To setup flux OK
Set Pr 25 and Pr 26 to the value required. Default values are set
relay
to switch at 10 % current, the same as FXM5.
50
Motor field is connected.
The Mentor II port on the FXMP25 is connected to the
Mentor II using a 10 way IDC to IDC ribbon.
The supply phases FXMP25 (L1 to L3) are in the same
phase as on the Mentor II (E1 to E3).
The field controller displays:
If the field controller trips, see Chapter 9
page 60.
Set parameter Pr 11 on FXMP25 to be the same value as
Pr 6.11 on Mentor II.
Set Pr 78 (Field mode) = 2.H (2) for Mentor II mode, half
control (ensure Pr 6.22 on Mentor II is set accordingly).
Set Pr 78 (Field mode) = 2.F (3) for Mentor II mode, full
control (ensure Pr 6.22 on Mentor II is set accordingly).
Press the mode button to enter parameter view mode.
Press and hold the mode button for at least 2 seconds to
carry out a reset.