Table 4-2 Typical cable sizes
Input/Output
1. Assumes the use of XLPE or EPR insulated cables in mounting method B2 as per
Table B52.5.
2. Assumes the use of 75 °C copper cable as per table 310.16 of the National
Electrical code.
4.5.1
Armature connections A1 A2
Connection to A1, A2 is only required in stand alone mode for voltage monitoring of the
armature voltage during field weakening. Armature branch fuses should be located
close to the armature supply and sized to protect the cable from the fuses to the
FXMP25. Cables 0.5 mm
4.5.2
Fusing for FXMP25
Table 4-3 Ferraz Shawmut internal semiconductor fusing*
Fuse type
10 x 38 mm ferrule
*Internal semiconductor fusing is for protection of SCR / thyristor bridge only.
Table 4-4 Ferraz Shawmut supply branch circuit protection fusing
Fuse type
14 x 51 mm ferrule
Table 4-5 Cooper Bussman supply branch circuit protection fusing
Fuse type
10.3 x 38 mm ferrule
Table 4-6 Siba supply branch circuit protection fusing
Fuse type
NH 000 knife blade
Recommended fuses are based on rated current operation. Supply branch circuit
NOTE
protection is required for cable and internal control electronics protection.
4.5.3
Internal semiconductor fuses
The internal semiconductor fuses provide protection to the FXMP25 SCR / thyristor
bridge only. The fuses can rupture if there is a fault in the field circuit. The user should
check the internal semiconductor fuses if the FXMP25 is tripping field loss (FdL) while
enabled.
Electric shock risk
If the FXMP25 controller has been energized, the supply must be isolated for at least
five minutes. This allows the internal capacitors to discharge fully before work may
WARNING
commence.
FXMP25 User Guide
Issue Number: 3
[1]
IEC 60364-5-52
2
4 mm
2
2
to 5.26 mm
(22 AWG to 10 AWG) should be used.
Rating
Rating
Vac
690
30
Rating
Rating
Vac
A
500
32
FR14GG50V32
Rating
Vac
600 V
Rating
Vac
690 V
www.controltechniques.com
UL508C/National Electrical Code
10 AWG
Catalog
A
number
FR10GB69V30
Catalog
Ref
number
number
W216656
Rating
Catalog number
A
30
Rating
Catalog number
A
32
[2]
Ref
number
M330015
UL Class J
alternative
LP-CC-30
20 477 13.32
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents