Torque Detection: L6
User constants for the torque detection function are shown in the following table.
Con-
stant
Number
Overtorque/
Under-
torque
detection
selection 1
L6-01
Torq Det 1
Sel
Overtorque/
Under-
torque
detection
L6-02
level 1
Torq Det 1
Lvl
Overtorque/
Under-
torque
detection
L6-03
time 1
Torq Det 1
Time
-64
5
Name
Description
Display
0: Overtorque/undertorque
detection disabled.
1: Overtorque detection only
with speed agreement;
operation continues after
overtorque (warning).
2: Overtorque detected
continuously during
operation; operation
continues after overtorque
(warning).
3: Overtorque detection only
with speed agreement;
output stopped upon
detection (protected
operation).
4: Overtorque detected
continuously during
operation; output stopped
upon detection (protected
operation).
5: Undertorque detection only
with speed agreement;
operation continues after
overtorque (warning).
6: Undertorque detected
continuously during
operation; operation
continues after overtorque
(warning).
7: Undertorque detection only
with speed agreement;
output stopped upon
detection (protected
operation).
8: Undertorque detected
continuously during
operation; output stopped
upon detection (protected
operation).
Open-loop vector control:
Motor rated torque is set as
100%.
V/f control: Inverter rated cur-
rent is set as 100%.
Sets the overtorque/under-
torque detection time in 1-sec-
ond units.
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
with
tion
0 to 8
0
No
A
0 to
150%
No
A
300
0.0 to
0.1 s
No
A
10.0
MEMO-
Open
Open
BUS
V/f
Loop
Flux
Loop
Regis-
Vec-
Vec-
Vec-
ter
PG
tor
tor
tor
1
2
A
A
A
A
4A1H
A
A
A
A
4A2H
A
A
A
A
4A3H
Page
6-53
6-53
6-54