YASKAWA Varispeed G7 Instruction Manual page 295

General purpose inverter (advanced vector control)
Hide thumbs Also See for Varispeed G7:
Table of Contents

Advertisement

Name
Con-
stant
Display
Number
Analog output 1
Sets the signal output level for
signal level
multi-function output 1 (terminal
selection
H4-07
FM)
0: 0 to +10 V output
AO Level
1: -10 to 10 V output
Select1
Channel 1 mon-
Effective when the Analog Moni-
itor selection
tor Board is used.
F4-01
Monitor selection:
AO Ch1 Select
Set the number of the monitor
item to be output. (U1-
Channel 1 gain
F4-02
Gain:
AO Ch1 Gain
Set the multiple of 10 V for out-
putting monitor items.
Channel 2 mon-
4, 10 to 14, 25, 28, 34, 39, 40 can-
itor selection
F4-03
not be set. 29 to 31 and 41 are not
AO Ch2 Select
used. When the AO-12 Analog
Monitor Board is used, outputs of
Channel 2 gain
± 10 V are possible. To output ±
10 V, set F4-07 or F4-08 to 1.
When the AO-08 Analog Monitor
F4-04
Board is used, only outputs of 0 to
AO Ch2 Gain
+10 V are possible.
A meter calibration function is
available.
Channel 1 out-
Sets the channel 1 item bias to
put monitor
F4-05
100%/10 V when the Analog
bias
Monitor Board is used.
AO Ch1 Bias
Channel 2 out-
Sets the channel 2 item bias to
put monitor
F4-06
100%/10 V when the Analog
bias
Monitor Board is used.
AO Ch2 Bias
Analog output
signal level for
0: 0 to 10 V
channel 1
F4-07
1: -10 to +10 V
AO Opt Level
Sel
Analog output
signal level for
0: 0 to 10 V
channel 2
F4-08
1: -10 to +10 V
AO Opt Level
Sel
Selecting Analog Monitor Items
The digital operator monitor items (U1-
terminals FM-AC and AM-AC. Refer to Chapter 5 User Constants, and set the values for the
(status monitor).
Alternatively, you can output monitor items (U1-
channels 1 and 2 on analog monitor boards AO-08 and AO-12. Refer to the table of constants, and set the val-
ues.
Setting
Description
Range
0 or 1
1 to 45
1 to 99
)
0.00 to
2.50
1 to 45
1 to 99
0.00 to
2.50
-10.0
to 10.0
-10.0
to 10.0
0 or 1
0 or 1
[status monitor]) are output from multi-function analog output
[status monitor]) from analog output option terminal
Control Methods
Change
Open
Factory
during
V/f
Loop
Setting
Opera-
V/f
with
Vector
tion
PG
1
0
No
A
A
A
2
No
A
A
A
1.00
Yes
A
A
A
3
No
A
A
A
0.50
Yes
A
A
A
0.0
Yes
A
A
A
0.0
Yes
A
A
A
0
No
A
A
A
0
No
A
A
A
Monitor Constants
MEMO
Open
BUS
Flux
Loop
Regis-
Vec-
Vector
ter
tor
2
A
A
423H
A
A
391H
A
A
392H
A
A
393H
A
A
394H
A
A
395H
A
A
396H
A
A
397H
A
A
398H
part of U1-
89
6-