Jog Frequency Operation Without Forward And Reverse Commands (Fjog/Rjog) - YASKAWA Varispeed G7 Instruction Manual

General purpose inverter (advanced vector control)
Hide thumbs Also See for Varispeed G7:
Table of Contents

Advertisement

Setting Precautions
To switch command inputs between the Communications Option Board and the control circuit terminals, set
the following constants.
Set b1-01 (Reference Selection) to 1 [Control circuit terminal (analog input)]
Set b1-02 (Operation Method Selection to 1 [Control circuit terminal (sequence inputs)]
Set one of the constants H1-01 to H1-10 (multi-function contact input terminal S3 to S12 function selec-
tion) to 2 (Option/Inverter selection).
Terminal Status
Jog Frequency Operation without Forward and Reverse Commands
(FJOG/RJOG)
The FJOG/RJOG command functions operate the Inverter using jog frequencies by using the terminal ON/
OFF operation. When using the FJOG/RJOG commands, there is no need to input the Run Command.
To use this function, set one of the constants H1-01 to H1-10 (multi-function contact input terminal S3 to S12
function selection) to 12 (FJOG command) or 13 (RJOG command).
Related Constants
Con-
stant
Number
d1-17
Note The unit is set in o1-03 (Frequency units of reference setting and monitor). The default for o1-03 is 0 (increments of 0.01 Hz).
* The setting range for open-loop vector 2 control is 0 to 66.0 (0 to 132.0 for PRG: 103 )
Multi-Function Contact Inputs (H1-01 to H1-10)
Set-
ting
Value
12
FJOG command (ON: Forward run at jog frequency d1-17)
13
RJOG command (ON: Reverse run at jog frequency d1-17)
Application Precautions
Jog frequencies using FJOG and RJOG commands are given priority over other frequency references.
When both FJOG command and RJOG commands are ON for 500 ms or longer at the same time, the
Inverter stops according to the setting in b1-03 (stopping method selection).
-84
6
Inverter
OFF
(Can be operated from frequency reference or control circuit terminal from analog input termi-
nal.)
Communications Option Board
ON
(Frequency reference and Run Command are enabled from Communications Option Board.)
Name
Description
Display
Jog frequency
The frequency reference when the
reference
jog frequency reference selec-
tion, FJOG command, or RJOG
Jog Reference
command is ON.
Frequency Reference and Run Command Selection
Change
Setting
Factory
Range
Setting
Opera-
0 to
6.00
400.00
Hz
*
Function
Control Methods
Open
during
V/f
Flux
Loop
V/f
with
Vec-
Vector
tion
PG
tor
1
Yes
Q
Q
Q
Q
Control Methods
Open
V/f
Loop
V/f
with
Vec-
PG
tor
1
Yes
Yes
Yes
Yes
Yes
Yes
MEMO
Open
BUS
Loop
Regis-
Vector
ter
2
Q
292H
Open
Flux
Loop
Vec-
Vec-
tor
tor
2
Yes
Yes
Yes
Yes