• Setting diverter valve activation time for DHW production (Password 303):
V3V timing rotation
020 sec
ESC
D
V3V timing rotation
020 sec
1
The fourth window of the DHW SETUP allows the installer to
set the rotation time of the 3-way diverter valve; this function
will keep the unit from triggering a fl ow switch alarm during
rotation of the 3-way diverter valve (this valve is used to divert
the production of water from the system to the DHW storage
tank); this window displays the following information:
A
- Diverter valve rotation time (
rotation of the diverter valves installed in the system; within
this time range, the heat pump which is activated for the
B
production of domestic hot water is OFF to avoid problems
with the fl ow switch.
C
From this window it is possible to:
(1) Set a rotation time for the diverter valve: pressing the key
C
will allow you to enter the modifi cation mode and the value will
be highlighted; by pressing the keys
to modify the value currently displayed, while pressing the key
will confi rm this choice.
(2) Pass on to the next window:
to go to the next window of this menu, press the key
(3) Go back to the previous window:
to go back to the previous window of this menu, press the
key
A
.
(4) Exit this window:
press the key
F
to return to the selection of the USER menus.
1
): indicates the time of
A
or
B
it will be possible
C
B
.
GB
4598010_00
41