IDEAL Evomax 30 Installation & Servicing Manual page 34

Evomax condensing boilers
Hide thumbs Also See for Evomax 30:
Table of Contents

Advertisement

42 EVomAX uSER IntERfACE - ADVAnCED oPERAtInG InStRuCtIonS
CHAnGInG tHE mAXImum fLoW tEmPERAtuRE SEtPoInt
Boiler default setting is that maximum flow temperature setpoint is 80°C
This feature limits the maximum flow temperature that can be set in the
Basic Operating Mode
Press SELECT and then hold + and - down together for more than 5s,
the following screen will be displayed
Installer Mode
normal operation
Set Flow Temp'
Set DHW Temp'
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
CH/DHW Priority
Set max flow temp'
Set Min Flow Temp'
Sys Frost Protect
Press SELECT and the following screen will be displayed
Set Max Flow Temp'
80°C
Press + and - to change to the required setting and then press
ENTER to store
Rotate the KNOB clockwise until Normal Operation is highlighted
again and press SELECT to return to normal operation
CHAnGInG tHE mInImum fLoW tEmPERAtuRE SEtPoInt
Boiler default setting is that minimum flow temperature setpoint is 30°C
This feature limits the minimum flow temperature that can be set in the
Basic Operating Mode
Press SELECT and then hold + and - down together for more than 5s,
the following screen will be displayed
Installer Mode
normal operation
Set Flow Temp'
Set DHW Temp'
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
Set Max Flow Temp'
Set min flow temp'
Sys Frost Protect
Soft Start Time
Press SELECT and the following screen will be displayed
Set Max Flow Temp'
30°C
Press + and - to change to the required setting and then press
ENTER to store
Rotate the KNOB clockwise until Normal Operation is highlighted
again and press SELECT to return to normal operation
34
InStALLAtIon
CHAnGInG tHE SyStEm fRoSt PRotECtIon tEmP. SEtPoInt
Note that System Frost Protection Function is only operational if an
Outside Sensor has been connected
The CH pump is switched on if the Outside Temp. is less than the System
Frost Protection Temp.
The CH pump is switched off if the Outside Temp. is more than the
System Frost Protection Temp. +5°C
The boiler default setting is the system frost protection temp. setpoint is -10°C
Press SELECT and then hold + and - down together for more than 5s, the
following screen will be displayed
Installer Mode
normal operation
Set Flow Temp'
Set DHW Temp'
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
Set Min Flow Temp'
Sys frost Protect
Soft Start Time
O/S Room Temp'
Press SELECT and the following screen will be displayed
Sys Frost Protect
-10°C
Press + and - to change to required setting, press ENTER to store
Rotate the KNOB clockwise until Normal Operation is highlighted
again and press SELECT to return to normal operation
CHAnGInG tHE Soft StARt tImE
The Soft Start Time is the time for which the boiler will run at the ignition
rate after a flame is detected
This feature helps make the boiler fully compatible with the CH/DHW
system. The default Soft Start time is 60s
Care should be taken in adjusting this feature as system noise and/or
boiler lockout could occur
Press SELECT and then hold + and - down together for more than 5s,
the following screen will be displayed
Installer Mode
normal operation
Set Flow Temp'
Set DHW Temp'
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
Sys Frost Protect
Soft Start time
O/S Room Temp'
DHW Sensor
Press SELECT and the following screen will be displayed
Soft Start Time
5s
Press + and - to change to required setting then press ENTER to store
Rotate the KNOB clockwise until Normal Operation is highlighted again
and press SELECT to return to normal operation
Note that the minimum setpoint after adjustment is 60s
continued . . . . . . . .
EVOMAX -
Installation & Servicing

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents