82 outSIDE SEnSoR fAuLt
Is the wiring securely connected at both the boiler and
Outside Sensor?
Disconnect the wires to the Outside Sensor. Check the
resistance using a suitable multimeter connected across
the thermistor's terminal pins.
At 0°C expect 32,000 - 33,000 W
At 10°C expect 19,000 - 21,000 W
At 20°C expect 12,000 - 13,000 W
Is the thermistor value correct?
Does the Outside Sensor wiring between the boiler
terminal strip and the PCB have continuity and is
securely connected?
Replace main PCB
83 FlOW/RETURN REVERSEd
Is the Pump connected the correct way?
Check that the system pipework is correct
EVOMAX -
Installation & Servicing
fAuLt fInDInG
yes
yes
yes
yes
no
Securely connect the wiring at both
the boiler and Outside sensor
no
Fit a new outside sensor
no
Ensure the wiring has continuity and is
securely connected
no
Reverse Pump
55