IDEAL Evomax 30 Installation & Servicing Manual page 17

Evomax condensing boilers
Hide thumbs Also See for Evomax 30:
Table of Contents

Advertisement

19 EXAMPlES OF CAlCUlATING FlUE RESISTANCES/lENGTHS - EXAMPlE 1
20 EXAMPlES OF CAlCUlATING FlUE RESISTANCES/lENGTHS - EXAMPlE 2
Example 2
Flue Size
Vertical Flue Kit 80/125
2 x 1m extension flue
2 x 45º elbow
Total Flue Resistance
The total maximum flue resistance for an Evomax 80 is 260 Pa or 12m
80/125. Therefore this installation is acceptable.
EVOMAX -
Installation & Servicing
InStALLAtIon
Example 1
Flue Size
Horizontal Wall Flue Kit 80/125
2 x 1m extension flue
1 x 90º elbow
Total Flue Resistance
The total maximum flue resistance for an Evomax 40 is 200Pa or 42m
80/125. Therefore this installation is acceptable.
Vertical Roof Flue for Evomax 80
Resistance (Pa) Resistance (m)
80/125
80/125
135
4.8
2 x (21.7)
2 x (1)
2 x (22)
2 x (1.1)
222
9
Horizontal Flue for Evomax 40
Resistance (Pa) Resistance (m)
80/125
80/125
45
7
2 x (4.8)
2 x (1)
14
1.6
68.6
10.6
17