Page 1
EVOMAX CONDENSING BOILER PRODUCT & FLUE GUIDE WE HAVE IT COVERED.
Page 2
Ideal Commercial Boilers is the UK’s market leader of high efficiency commercial heating solutions. Operating from its Hull manufacturing plant and offices since 1906, Ideal Commercial Boilers is one of the few true British manufacturers left in the heating industry. BRING BOILERS...
Page 4
EVOMAX 30 - 150kW *5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
Page 6
• NOx <40mg/kWh (Class 5) for all natural gas models for maximum BREEAM points DOWNLOAD THE APP *5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.
‘A’ ‘C’ ‘B’ DIMENSIONS & CLEARANCES BOILER DIM A DIM B DIM C 30, 40, 60, 80 100, 120 All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP: DEPENDENT SIDES: 25mm ON FLUE SIZE FRONT: 450mm BOTTOM:...
SUGGESTED ENGINEERING SPECIFICATION OVERVIEW MOUNTING The boilers must be fully automatically controlled, wall The condensing boilers can be installed either on the wall or into a prefabricated floor mounted frame. Wall mounted, fanned, super-efficient condensing appliances brackets must be located at the top of the boiler and utilising an aluminium silicon alloy heat exchanger and be visible from the front to aid installation.
FLUE SYSTEMS A comprehensive range of flue kits are available from The resistance of flue components, together with the Ideal Commercial Boilers including horizontal and vertical maximum flue resistance each boiler can work against, may concentric and open flue options.
EVOMAX CASCADE FRAME & HEADER KITS BOILER FRAME AND HEADER KITS The Frame and Header Kits are suitable for modular (cascade) boiler installations, and are available up to a maximum output of 600 kW, in both in-line and back-to-back arrangements. IN-LINE KITS Kits include flow &...
Page 18
5 X EVOMAX 30 - 120 KW HEIGHT LENGTH DEPTH CONCENTRIC HEADER KITS RATING DN FLANGE SIZE (mm) (mm) (mm) FLUE 30-80kW 1945 2750 DN100 80/125 UIN209805 100kW 1945 2750 DN100 100/150 UIN209804 120kW 1945 2750 DN100 100/150 Measurements are without boilers attached. 100-120kW boilers are deeper than Frame and Header Kit.
Page 19
FRAME & HEADER KITS SYSTEM DESIGN OPTIONS FRAME/ SIDE BY SIDE HEADER KIT BACK TO BACK TOTAL OUTPUT SIDE BY SIDE OPTION BOILER HEADER FOOTPRINT SIZE PRODUCT NO. FOOTPRINT SIZE REQUIRED KW OF BOILERS – BOILER MODELS MODELS PRODUCT NO. W X D (MM) SIDE BY SIDE W X D (MM)
Page 20
SYSTEM DESIGN OPTIONS - CONTINUED SIDE BY SIDE HEADER KIT BACK TO BACK FRAME/HEADER TOTAL OUTPUT NO. OF SIDE BY SIDE OPTION – BOILER FOOTPRINT SIZE PRODUCT NO. FOOTPRINT SIZE PRODUCT NO. REQUIRED KW BOILERS BOILER MODELS MODELS W X D (MM) SIDE BY SIDE W X D (MM) BACK TO BACK...
& pipe work connector, all isolation valves, pressure relief valve, drain cock and associated fittings • The Low Height Frame and Header Kit can be installed with either an Ideal Commercial Sequencer offering direct modulation of the system, reducing running costs, or a proprietary option •...
Page 22
LOW HEIGHT FRAME & HEADER KITS 1 X EVOMAX 30 - 150 KW HEIGHT LENGTH DEPTH DN FLANGE CONCENTRIC HEADER KITS (mm) (mm) (mm) SIZE FLUE 30-80kW 1550 80/125 DN50 100-120kW 1550 100/150 (2”BSP) 150kW 1550 100/150 Measurements are without boilers attached. 150kW boilers are deeper than Low Height Frame and Header...
Page 23
LOW HEIGHT FRAME & HEADER KITS SYSTEM DESIGN OPTIONS SIDE BY SIDE TOTAL OUTPUT NO. OF OPTIONAL LOW FRAME/HEADER HEADER FOOTPRINT SIZE BOILER MODELS REQUIRED KW BOILERS LOSS HEADER PRODUCT NO. W X D (MM) DN50 550 x 642 209394 210012 DN50 550 x 642...
Page 24
SYSTEM DESIGN OPTIONS - CONTINUED SIDE BY SIDE TOTAL OUTPUT NO. OF OPTIONAL LOW FRAME/HEADER HEADER FOOTPRINT SIZE BOILER MODELS REQUIRED KW BOILERS LOSS HEADER PRODUCT NO. W X D (MM) DN80 1650 x 642 252437 2 x 100 + 1 x 30 210020 DN80 1650 x 642...
Page 25
SYSTEM LAYOUT TYPICAL SYSTEM BOILER LAYOUT * Low loss header may not be required depending on system design and pump sizing...
Page 28
• Increaser • Wall plates (x2) To comply with CE certification, Evomax boilers must be fitted with Ideal concentric flues (when using concentric flue type). VERTICAL ROOF FLUE KIT EVOMAX VERTICAL CONCENTRIC FLUE APPLICATION ~ MAXIMUM LENGTHS AND PRESSURE DIFFERENTIALS...
Page 29
** At least 1 off extension tube MUST be used in the installation. This may be suitably cut to length if required. To comply with CE certification, Evomax boilers must be fitted with an Ideal boiler adapter. • B type flues must use the inlet grille.
Page 31
FLUE RESISTANCES FLUE SYSTEMS For concentric flue systems with elbows fitted, use the table to correct the maximum flue extension capability. Alternatively use the table to design the flue system, deducting the individual resistance of components from the maximum pressure drop allowed in the flue for that boiler. The maximum pressure drop allowed in the flue is given below.
Page 32
FOR OWN BUILT OPEN FLUE USE THIS: MAXIMUM ALLOWABLE PRESSURE DIFF & FLUE LENGTH FLUES INCLUDING TERMINAL MODEL FLUE SIZE PRESSURE DIFF (Pa) 30/30P 80/125 40/40P 80/125 80/125 60/60P 100/150 80/80P 80/125 100/150 100/150 100/150 EXAMPLES OF CALCULATING FLUE RESISTANCES/LENGTHS EXAMPLE 1 (CONCENTRIC) HORIZONTAL FLUE FOR EVOMAX 40 Resistance (m)
Page 33
2 x 0.85 = 1.7 Total Flue Resistance 12 - 1.7 = 10.3 Therefore this installation is acceptable as only a 3m run. EXAMPLE 3 (OPEN FLUE) OPEN FLUE FOR EVOMAX 30 Resistance (m) Flue Size Max permissible flue run 2 x 45˚ elbow 2 x 0.45 = 0.9...
MULTILINE FLUE CASCADE. The Multiline Flue Cascade is one of the latest additions to the flue accessory range from Ideal, designed specifically for the Evomax range. Available for installations up to 600kW as both a starter kit and extension pack The Multiline Flue Cascade is one of latest additions to the fl...
Page 35
Flue height = 570mm from the top of the first boiler in the system. Increase the height 29mm for each adjacent boiler. DESCRIPTION 715mm Evomax Multiline 686mm 657mm 210264 5022142102645 628mm 599mm Starter Kit 80/125 570mm Evomax Multiline 210265 5022142102652 Extension Kit 80/125 Evomax Multiline 5022142102683...
Page 36
EVOMAX PLUME KIT The Evomax Plume Kit is one of the latest additions to the flue accessory range from Ideal, designed specifically for the Evomax range. Available for Evomax boilers up to 120kW the Plume Kit can be used to relocate the flue terminal up to 10m.
Page 38
FLUE TYPES Before ventilation can be sized we need to identify the type of flue system. Type B – Open flue Type C – Room sealed We also need to know the classification of the room type. • Boiler house – a dedicated building for the installation of boilers and ancillary plant. •...
Page 39
Where 2 or more gas fired boilers are connected to a common natural draught flue, the boilers must be installed in the same room and have the same type of burner system. A gas fired boiler and a solid fuel or biomass boiler must not discharge into the same flue.
Page 40
GUIDE TO FLUE INSTALLATION & REGULATIONS There are many different regulations relating to flues and ventilation. This document will not cover all of them but assist in obtaining information and guidance, and provide useful and practical information. This guide looks at common standards used to determine the requirements for flue and ventilation installation requirements and should not be used as a sole reference for flue regulations.
Page 41
WHEN SHOULD I USE COMMERCIAL FLUE REQUIREMENT LEGISLATION AND GUIDANCE? BS5440 covers domestic installations up to 70kW net input, however if an appliance is to be installed in a factory location even if under 70kW then the commercial requirements of IGE UP10 & BS6644 must be adopted. Similarly if a cascade boiler installation is fitted and the total input exceeds 70kW then the commercial flues and ventilation should be adopted.
Page 42
TERMINATION POSITIONS APPLIANCES OVER 70kW NET INPUT SEE IGEM 10 FOR FURTHER DETAILS 1, 3 & 6 Minimum Height of Termination Located on a roof 70kW 80kW 100kW 120kW 150kW 200kW 240kW 300kW Natural Draught 600mm 615mm 645mm 676mm 722mm 798mm 859mm 950mm...
Page 43
VENTILATION REQUIREMENTS OF COMMERCIAL BOILERS OVER 70kW NET INPUT OPEN FLUED APPLIANCES, TYPE B & C IN PLANT ROOMS VENTILATION DIRECT TO OUTSIDE AIR (cm² per kW net heat input) FLUE TYPE HIGH OPEN (TYPE B) OPEN (TYPE C) OPEN FLUED APPLIANCES, TYPE B IN PLANT ROOMS (ADDITIONAL RECOMMENDATIONS) Natural Ventilation cm²...
Heating Systems. additives MUST be removed by thorough cleansing. BS 7593:2006 details the steps necessary to clean a domestic If water treatment is used Ideal Boilers recommend only the heating system. use of Scalemaster Gold 100, Fernox, MB-1, Adey MC1, 3.
DOMESTIC BOILERS (UP TO 70kW) BS5440 Flues and ventilation for gas appliances of rated input not exceeding 70 kW net (1st, 2nd and 3rd family gases). Specification for the installation and maintenance of ventilation provision for gas appliances. In I.E refer to I.S. 813. FLUE TERMINATION POSITION Due to the high efficiency of these boilers pluming will occur.
Page 46
All vents must be permanent with no means of closing, and positioned to avoid accidental obstruction by blocking or flooding. EVOMAX 30/30P, 40/40P, 60/60P Detail reference should be made to BS. 5440 Pt. 2. In IE refer to the current edition of I.S. 813.
HERE FOR YOU. At Ideal, we are committed to delivering the highest levels of customer service. With over a century of experience in the heating industry, we know how important confidence and trust is to our customers. You can be confident to know that you’re partnering with a British manufacturer that’s supported by a dedicated national service team, delivering help and...
Page 52
Statutory rights of the consumer are not affected. PLEASE NOTE: The information in this brochure was correct at the time of going to print. Ideal Commercial Boilers reserve the right to make any modifications to product specifications or any other details, without prior notification. For further clarification, please enquire in writing to the head office address (address below).