Comparison Table Of Function - Mitsubishi Electric G-50A Technical Manual

Air conditioning network system centralized controller g-50a and integrated centralized control software tg-2000a
Hide thumbs Also See for G-50A:
Table of Contents

Advertisement

2.2 Comparison table of function

Table 4-2 compares the function of G-50A unit, Web browser and TG-2000A as follows.
: per unit
:per group
Item
Start/stop
Start/stop
Operation mode
Cool (Dry)/Heat/Fan/Auto
Set
Set temperature range (Unit 1°C)
temperature
Cool (Dry) : 19°C ~ 30°C
Heat
: 17°C ~ 28°C
Auto
: 19°C ~ 28°C
Set
With the local remote controller (ME remote
temperature
controller), the lowest temperature is limited
range limiting
to that above 19°C at cooling (dry) and the
function
highest temperature below 28°C at heating.
Air velocity
Air velocity
switching
(Hi/Med. 1/Med. 2/Lo)
Air direction
Air direction:
switching
Vertical/swing/fixed louver
Prohibition of local
Prohibited items
remote controller
Start/stop, Operation mode,
operation
Set temperature, Filter resetting
Group
registration
Filter sign
Monitoring/displaying of filter sign,
allowing reset operation after cleaning.
Abnormality
Displays the condition of
of air
abnormality/normal of air
conditioner
conditioners, and allows to release
the abnormality.
Schedule
[Weekly schedule]
Set unit: 1 minute
Daily operation frequency: 12 times
Items: Start/stop, Operation
mode, Set temperature,
Local control prohibition
[Annual schedule]
Allows setting a special day for 50 times a year.
[Daily schedule]
Allows changing daily schedule only
without changing weekly/annual schedules.
[Weekly schedule]
Set unit: 10 minute
Daily operation frequency: 3 times
Allows setting start/stop pattern
for 3 times and permit/prohibition
pattern for 1 time.
Interlocked
Interlocked setting of indoor unit
ventilation
with ventilation equipment (Lossnay)
Ventilation
Switching the stop/Lo/Hi of interlocked
switching
ventilation equipment (Lossnay).
Malfunction
Observing malfunction history
record
record about air conditioners.
Operation
Observing operation history
record
record about air conditioners
Integrated
Observing integrated operation
operation
time per indoor unit.
1
time*
Allows printer and file outputting.
Electric power
Apportioning the electric power consumed
apportioning
by air conditioners based on the operation
1
function*
time of indoor /outdoor units.
*1 This is valid only when the week schedule/year schedule license is registered.
*2 This is valid only when the electric power division license is registered.
*3 Up to 64 error contents can be checked for unit errors and communication errors respectively.
*4 Up to 3000 errors including errors (and others) detected by TG-2000A as well as unit errors and communication errors detected by G-
50A can be recorded. They can also be output in CSV format.
*5 10000 cases of the contents operated from TG-2000A can be recorded.
*6 Error release operation unit is as shown in the table, and all the erroneous units of G-50A system where error release operation is made
are released.
*7 Please refer to section 2,3 for function licence.
12
Table 2-4 Function comparison table
: per block
: per G-50A
Content
G-50A
(Reset)
(Releasing
abnormality)
(Switching)
:per floor
: for whole building
7
Controlling*
Web browser
TG-2000A
(Reset)
(Reset)
6
6
*
*
(Releasing
(Releasing
abnormality)
abnormality)
(Switching)
(Switching)
(Charge block)
: Unable to comply with
Monitoring*
G-50A
Web browser
(Grouping
(Grouping
information
information
monitor)
monitor)
6
*
(64 cases)
(64 cases)
: Not provided
7
TG-2000A
(Grouping
information
monitor)
(3000 cases)
Allows outputting
3
*
*
4
CSV file.
(10,000 cases)*
5
(Charge block)