7.1 Weekly schedule using the G-50A

The following explains the outlines the weekly schedule set using the G-50A.
If the weekly schedule is set using the G-50A, setting is required to be performed using the G-50A for
every G-50A unit.
1The timetable for start/stop can be set in increments of 10 minutes.
2For the daily operation schedule, up to 3 settings for each of the start and stop times for operation
can be set.
These settings can be set per group as P1, P2, and P3 as
schedule patterns at the local remote controller.
3In addition, it is possible to set the schedule for the same day by combining the start/stop operation
prohibition schedule patterns. (
4As the contents of the set schedule can be saved to memory, copying schedule patterns to other
groups is easy.
5Settings can be performed to set the temperature and setback operation-1 while schedule operation
is being executed.
P4
P3
P2
P1

7.2 Annual/weekly schedule using web monitoring

Registering the weekly/annual schedule license number in the G-50A main unit using the PC's browser,
will enable this function. In this case, the weekly schedule of the G-50A will be invalidated.
Using this function, the schedule for every G-50A unit is set with the web browser software.
[Weekly schedule]
1Settings can be performed in 1-minute increments.
2The number of setting items is 12 times per day (for every day of the week). Settings allowing
operation mode only or set temperature only are possible too.
3Set items include the operation prohibition for start/stop, operation mode, set temperature, and local
remote controller.
4Setting subjects include the setting per group, per block, and of all groups.
[Annual schedule]
150 special days can be set up to 24 months ahead, including this month.
2Setting subjects include the setting per group, per block, and of all groups.
3Up to 5 schedule patterns can be set. (Contents of the settings are similar to the weekly schedule)
In addition, during the days set by the annual schedule, the regular weekly schedule will not be
executed.
1
The setback value allows the set temperature to be altered only by the difference compared to the standard temperature, to help save energy.
Example: When the standard temperature is 24°C and the setback value is 2°C.
During operation as a cooler, the set temperature is 24°C + 2°C = 26°C.
During operation as a heater, the set temperature is 24°C - 2°C = 22°C.
P1
,
P2
,
PROH.
PERM.
ON
OFF
ON
OFF
ON
OFF
24°C
0 8 : 0 0
1 0 : 0 0
23°C
1 3 : 0 0
1 7 : 0 0
– – : – –
2 2 : 0 0
Four preprogrammed settings
Figure 7-1 G-50A schedule screen configuration
P4
P3
)
(SCHEDULE)
(SCHEDULE)
(SCHEDULE)
(SCHEDULE)
G01
(SCHEDULE)
G01
Assigned for each group by day of the week
(1 type) of the operation prohibition
MON
1 0 : 3 5
MON
1 0 : 3 5
MON
1 0 : 3 5
MON
1 0 : 3 5
MEETING1
MON
1 0 : 3 5
MEETING1
SU MO TU WE TH FR SA
patterns
1
2
2
3
3
1
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tg-2000a

Table of Contents