13. Step 10: Determination of Address for Air Conditioning
Instrument and PC for Control

13.1 Address Setting for Air Conditioning Instrument

Address setting range for various types of air conditioning instrument is shown in the table below.
Address range
000
G-50A
001~050
Indoor unit, OA Processing Unit, Lossnay, M-
NET interface
051~100
Outdoor unit, BC controller, constant-capacity
unit, heat storage tank unit
101~150
Master remote control (M-NET remote control)
151~200
Slave remote control (M-NET remote control)
201~250
System remote control (PAC-SF44SRA)
ON/OFF remote control (PAC-YT40ANRA)
Group remote control (PAC-SC30GRA) and others
Address range
001~050
Indoor unit, remote controller (group number)
201~250
K-transmission converter (PAC-SC25KAA)
Address range
001~050
Outdoor unit (adapter for M-NET connection)

13.2 Setting of LAN System

The components shown in Table 13-4 are required for LAN connection
Names of components
Hub for 10BASE-T (for 5 ports)
Hub for 10BASE-T (for 8 ports)
Hub for 10BASE-T/100BASE-Tx
(for 5 ports)
Hub for 10BASE-T/100BATSE-Tx
(for 8 ports)
LAN straight cable (twist pair cable)
for 10BASE-T
LAN straight cable (twist pair cable)
for 100BASE-Tx
Table 13-1 Address setting range for M-NET models
Models
Table 13-2 Address setting range for K-control model
Models
Table 13-3 Address setting range for A-control model
Model
Table 13-4 Components required for LAN
1 port among 5 ports is available for cascade changeover.
1 port among 8 ports is available for cascade changeover.
The allowable maximum wiring length is 100m in connection. Also, twist pair cable is subject to a
standard for category sorting stipulated by EIA/TIA. Twist pair cable in accordance with category
3 and 5 is used for Ethernet, but one in accordance with category 5 is recommended.
Over-the-counter LAN cable is in accordance with category 5 and either 10BASE-T or
100BASE-Tx is available.
This cable is used for connection to optical cable, of which adaptable category is 5 and of which
form is the same as for 10BASE-Tx.
Remarks
Basically, the address range of G-50A is fixed to "000" at the factory.
M-NET remote control includes ME remote control, compact
remote control, and Lossnay remote control to connect to M-NET
transmission line.
When MA remote control is used, address setting is not
necessary.
G-50A can also be used within the address range shown at the
left.
Remarks
Minimum address for 200+K-control model indoor unit
Remarks
Address for refrigerant system is to be set up separately.
Remarks
85