Step 6: Energy Saving/Peak Cut Control - Mitsubishi Electric G-50A Technical Manual

Air conditioning network system centralized controller g-50a and integrated centralized control software tg-2000a
Hide thumbs Also See for G-50A:
Table of Contents

Advertisement

9. Step 6: Energy Saving/Peak Cut Control

Here the energy saving control or peak cut control to be performed by G-50A is set.
This setting is essential in conducting the energy saving control or peak cut control.
As this function is optional, the license registration to G-50A is necessary to use.
A different license should be applied to the energy saving control and peak cut control respectively, the
license for your desired usage should be registered.
- Energy saving setting
- Monitoring of current energy saving
state
PC for centralized
control (Integrated
software)
Collects daily
power
consumption
For PLC, the pulse counting software (Ver. 1.01 ~ ) used for the power apportioning
Notice
function can be applied. (Pulse counting software: PAC-YG11CDA, etc. installed)
For the pulse counting software used at peak cut control, employ that Ver. 1.01 or
later.
For the peak cut control, use one set of watt-hour meter for each G-50A.
The peak cut control license contains the function of energy saving control.
Peak cut control is not available in RS-485WHM system.
CAUTION
Figure 9-1 Energy saving/peak cut control system composition
[Re: Energy saving/peak cut function]
During the use of the peak cut function, any damage such as the exceeding of
power consumption than the contract demand should induced due to the trouble
of G-50A or PLC, such damage will not be indemnified, for which your kind
understanding is requested.
The registration of
energy saving control
or peak cut control is
necessary.
G-50A
Collects current
- Capacity saving control
daily consumption
(60/70/80/90%)
(every per minute)
PLC
(Pulse counting
software installed)
(*Requires to execute the peak cut control)
- Set temperature control (±2˚C)
- Fan (thermostat OFF) control
- Stopping control
Watt-hour
meter
Counts for electric power pulse
61