Interrogating Power Failure Recognition Time; Sound Alarm Monitoring; Programming Sound Alarm Sensitivity - Phonetics Sensaphone 800 User Manual

Remote monitoring system
Table of Contents

Advertisement

Sensaphone
Model 800 User's Manual
®

5.9.2 Interrogating Power Failure Recognition Time

1. Press WHAT IS.
WHAT
IS
2. Press RECOGNITION TIME.
7
RECOGNITION
TIME
3. Press POWER.
0
ID NUMBER
POWER
The Model 800 will recite the power Recognition Time.

5.10 Sound Alarm Monitoring

This feature allows you to program the level and duration of
sound that will cause the Model 800 to respond to an alarm and
dial-out. It may be useful to desensitize the Model 800 to sound
if it is installed in an area with a relatively high noise level, or
where a loud noise occurs frequently but is not associated with an
alarm. In some applications, it may be desirable to increase sound
sensitivity to low sound levels.

5.10.1 Programming Sound Alarm Sensitivity

The sensitivity setting for sound alarm monitoring ranges from 1
to 160. A value of 1 makes the microphone the MOST sensitive
to changes in sound. The value 160 makes the microphone the
LEAST sensitive to sound. The default value is 32.
1. Press SET.
SET
2. Press CALIBRATE.
6
CALIBRATE
3. Press SOUND. The Model 800 responds: "Enter number."
9
LISTEN TIME
SOUND
81