Phonetics Sensaphone 800 User Manual page 110

Remote monitoring system
Table of Contents

Advertisement

Sensaphone
Model 800 User's Manual
®
Step 3: Connect cable from thermostat to Sensaphone 800.
This Sensaphone 800 has a terminal strip below the input/output
wiring door that will connect to the 12VDC power supply and X
& C terminals of the thermostat (See Figure 1). This connection
is required to switch the thermostat between normal and vacation
modes. Run a two-conductor cable from the thermostat to the
Model 800. On the thermostat, connect the red wire to the X (+)
terminal, and the black wire to the C (-) terminal. On the 800,
connect the red wire to the NO terminal. Connect the black wire
to the negative wire from the power supply. Use a wire nut to
complete this connection. Connect the positive wire from the
power supply to the "C" terminal on the model 800.
����������
Step 4: Program the Thermostat.
Refer to the manufacturers instructions for programming the
thermostat. Be sure to program settings for both normal and
vacation modes.
Controlling the Thermostat
The operating mode of the thermostat (normal/vacation) can be
controlled at the Model 800 keypad or remotely via Touch-Tone
comands. Both methods are described below:
107
� ��
� �
� ��
� �
� �
�������� ��������� �����
� �
� �
������
���
�����
��
��
�����
����� ������

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents