Interrogating Voice Repetitions; Intercall Time; Programming Intercall Time; Interrogating Intercall Time - Phonetics Sensaphone 800 User Manual

Remote monitoring system
Table of Contents

Advertisement

3. Using the number keys, enter a value from 1 to 10.
1
CALL
DELAY
4
MAX CALLS
7
RECOGNITION
TIME
4. Press ENTER. The Model 800 will respond: "Enter."
ENTER
PM

4.11.2 Interrogating Voice Repetitions

To interrogate Voice Repetitions:
1. Press WHAT IS.
WHAT
IS
2. Press VOICE REPS.
2
VOICE
REPS
The Model 800 will recite the number programmed.

4.12 Intercall Time

The Intercall Time is the programmable period of time the
Model 800 waits in calling subsequent telephone numbers.
Intercall Time is activated only after alarm dial-out to the first
telephone number fails to be acknowledged. This period can be
programmed from 10 seconds to 60 minutes. The default intercall
time is 1 minute.
If an incoming telephone call is made to the Model 800 during
Intercall Time (in between its dialing of subsequent telephone
numbers to report an alarm), it will answer the incoming call and
immediately report any existing alarms.
Chapter 4: Communications Programming
2
3