Remote monitoring system
Table of Contents

Advertisement

Sensaphone
Model 800 User's Manual
®
2. Press STATUS.
STATUS
The Model 800 audibly recites the current status of every zone. In
a Status Report, each zone is first identified by its zone number,
followed by a report that specifies parameters currently affecting
that zone. If a zone is disabled, the word "Alarm Disabled"
immediately follows the number recited for that zone.
For example, zone 3 is configured as a normally open, dry contact
zone. During the Status Report:
• If disabled, the Model 800 recites:
"Zone 3, the Alarm is Disabled" for zone 3.
• If enabled, the Model 800 recites:
"Zone 3—OK," for zone 3.
In another example, zone 2 is configured as a temperature zone.
The current temperature is 76 degrees. During a Status Report:
• If disabled, the Model 800 recites:
"Zone 2, the alarm is disabled, it is now 76 degrees
fahrenheit—OK"
• If enabled, the Model 800 recites:
"Zone 2—76 degrees fahrenheit—OK."

5.3 Zone Recognition Time

The Zone Recognition Time is the length of time an alert
condition must be present before a valid alarm exists and dial-out
is activated. This time period is programmable, from 0 minutes, 0
seconds (for immediate response) up to a period of 540 minutes,
0 seconds. If an alert condition begins and then clears within the
established Recognition Time, no dial-out will occur. When an
alert condition continues beyond the programmed Recognition
Time, the Model 800 initiates dial-out. The default setting for
Zone Recognition Time is 0 minutes, 3 seconds.

5.3.1 Programming Zone Recognition Time

1. Press SET.
SET
71