Technical specifications

Environmental conditions

Ambient temperature
Storage temperature
Protection class
Maximum humidity level
Shock and vibration
Operating altitude
Environmental classes
Minimum mounting clearance
Standards
CE marking
UL certification (UL508C)
CTick marking
ISO 9001
64
0 ... 40 °C: without derating
40 ... 60 °C: with derating
-40 ... + 70 °C
IP 20
95 % (non-condensing)
Long-term storage in the transport packaging according to EN 60721-3-1 Class 1M2
Transport in the transport packaging according to EN 60721-3-2 Class 2M3
Vibration during operation according to EN 60721-3-3 Class 3M2
Up to 4000 m above sea level
1000 ... 4000 m: output current derating
2000 ... 4000 m: input voltage derating
Pollution class: 3S2
Gas class: 3C2 (SO
, H
2
2
Climate class: 3K3
Top: 100 mm
Bottom: 100 mm (85 mm for fan-cooled frame size A)
Side: 0 mm
European Low Voltage Directive (EN61800 -5-1 and EN 60204-1)
European EMC Directive (EN 61800 - 3)
S)
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127