Setting application macros
Application macro AP010 - Simple pump applications
Parameter
Description
P1080[0]
Minimum frequency
P1300[0]
Control mode
P1110[0]
BI: Inhibit negative frequency setpoint
P1210[0]
Automatic restart
P1120[0]
Ramp-up time
P1121[0]
Ramp-down time
Application macro AP020 - Simple fan applications
Parameter
Description
P1110[0]
BI: Inhibit negative frequency setpoint
P1300[0]
Control mode
P1200[0]
Flying start
P1210[0]
Automatic restart
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127
M M
M M
M M
Factory
default
0
0
0
1
10
10
Factory
default
0
0
0
1
4.3 Quick commissioning
OK
OK
Default for
Remarks
AP010
15
Inverter running at a lower speed
inhibited
7
Quadratic V/f
1
Reverse pump rotation inhibited
2
Fault acknowledgement at
power-on
10
Ramp-up time from zero to
maximum frequency
10
Ramp-down time from maximum
frequency to zero
Default for
Remarks
AP020
1
Reverse fan rotation inhibited
7
Quadratic V/f
2
Search for the speed of the
running motor with a heavy
inertia load so that the motor
runs up to the setpoint
2
Fault acknowledgement at
power-on