Connection macro Cn008 - PID control with analog reference
NOTICE
If a negative setpoint for the PID control is desired, change the setpoint and feedback
wiring as needed.
When you switch to Hand mode from PID control mode, P2200 becomes 0 to disable the
PID control. When you switch it back to Auto mode, P2200 becomes 1 to enable the PID
control again.
Connection macro settings:
Parameter
Description
P0700[0]
Selection of command source
P0701[0]
Function of digital input 1
P0703[0]
Function of digital input 3
P2200[0]
Enable PID controller
P2253[0]
CI: PID setpoint
P2264[0]
CI: PID feedback
P0756[1]
Type of AI
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1
P0732[0]
BI: Function of digital output 2
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127
10V AI1 AI2 0V DI1 DI2 DI3 DI4 DIC 24V 0V
0V
0V
AO+ AO- DO1+ DO1-
220V
N
0~20mA=
0~50/60Hz
DO2
P+ N-
Factory
Default for
default
Cn008
1
2
0
1
9
9
0
1
0
755.0
755.0
755.1
0
2
21
21
52.3
52.2
52.7
52.3
Commissioning
4.3 Quick commissioning
M M
OK
OK
PID controller
Remarks
Terminals as command source
ON / OFF
Fault acknowledgement
Enable PID
PID Setpoint = Analog input 1
PID feedback = Analog input 2
Analog input 2 0 ... 20 mA
Actual frequency
Inverter running
Inverter fault active