Commissioning
4.3 Quick commissioning
Connection macro Cn007 - External push buttons with analog control
Note that the command sources are pulse signals.
Connection macro settings:
Parameter
Description
P0700[0]
Selection of command source
P1000[0]
Selection of frequency
P0701[0]
Function of digital input 1
P0702[0]
Function of digital input 2
P0703[0]
Function of digital input 3
P0704[0]
Function of digital input 4
P0727[0]
Selection of 2 / 3-wire method
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1
P0732[0]
BI: Function of digital output 2
40
0~10V=
0~50/60Hz
10V AI1 AI2 0V DI1 DI2 DI3 DI4 DIC 24V 0V
0V
0V
AO+ AO- DO1+ DO1-
220V
N
0~20mA=
0~50/60Hz
DO2
P+ N-
Factory
Default for
default
Cn007
1
2
1
2
0
1
0
2
9
12
15
9
0
2
21
21
52.3
52.2
52.7
52.3
M M
OK
OK
Remarks
Terminals as command source
Analog
OFF hold
Forward pulse + ON
Reverse pulse + ON
Fault acknowledgement
3-wire
STOP + Forward pulse + Reverse
pulse
Actual frequency
Inverter running
Inverter fault active