Terminal Position - Ferroli TEMPRA 30 Installation, Service And User Instructions Manual

Copper wall-mounted system, gas fired boiler for central heating, fan assisted, room sealed compartment, electronic flame ignition and control
Table of Contents

Advertisement

CLEARANCES:
* 600mm minimum clearance for servicing
access
Top clearance only applies to 100Ø concen-
tric fl ue system

Terminal Position

Minimum dimensions of fl ue terminal positions
Dimensions
A
Directly below an opening, air brick, opening windows, etc.
B
Above an opening, air brick, opening windows, etc.
C
Horizontally to an opening, air brick, opening windows, etc.
D
Below gutters, soil pipes or drain pipes
E
Below eaves
F
Below balconies or car port roof
G
From a vertical drain pipe or soil pipe
H
From an internal or external corner
I
Above ground roof or balcony level
J
From a surface facing the terminal
(also see 6.1.2)
K
From a terminal facing the terminal
L
From an opening in the car port ( e.g. door,
window) into the dwelling
M
Vertically from a terminal on the same wall
N
Horizontally from a terminal on the same wall
O
From the wall on which the terminal is mounted
P
From a vertical structure on the roof
Q
Above intersection with roof
NOTE N/A = Not applicable
a
I
n addition, the terminal should not be nearer than 150 mm (fanned draucht) or 300 mm (natural draught) to an opening in the building fabric
formed for the purpose of accommodating a built-in element such as a window frame.
Fig. 8
J
Terminal position
(kW input expressed in net)
TEMPRA 30
5 min.
460
5 min.
P
D, E
B
C
G
A
Balanced flues room
sealed
Fanned
draught
300 mm
300 mm
300 mm
75 mm
200 mm
200 mm
150 mm
300 mm
300 mm
600 mm
1200 mm
1200 mm
1500 mm
300 mm
N/A
N/A
N/A
363
50 mm
600* min.
N
N
Fig. 9
11