Copper wall-mounted system, gas fi red boiler for central heating, fan assisted, room sealed compartment, electronic fl ame ignition and control (48 pages)
Page 1
MAXIMA 35 C wall-mounted gas fi red, pre-mix condensing combination boiler INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE G C N° 47-267-33...
“This record must be completed and left with the end user”. Ferroli is a member of the Benchmark initiative and fully supports the aims of the programme. Benchmark has been introduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency.
1.1 Introduction Dear Customer, Thank you for choosing Maxima 35 C, a FERROLI wall-mounted boiler of the latest generation, featuring advanced design and cutting-edge technology. Maxima 35 C is a high-efficiency condensing pre-mix appliance for heating and hot water production with extremely low emissions, running on natural gas or LPG.
Maxima 35 C 1.2 Control panel 15 13 fig. 1 1 - Summer/Winter selection key In Winter mode, both heating and hot water production are on; in Summer mode, hot water production only (the heating display information will disappear in summer mode and the summer display will illuminate - item 20).
Page 6
Maxima 35 C 13 - Fan symbol This appears when there is a call for heating or hot water, and the fan is operating. 15 - Ignition symbol The ignition symbol appears during the ignition phase. 16 - Flame symbol Indicates the burner is on, the small rising bars to the right indicate the burner output 1=low, 5=high.
Maxima 35 C 1.3 Operationg instructions Ignition • Open the gas isolation valve upstream of the boiler. • Purge the air from the pipe upstream of the gas valve. • Ensure power is on to appliance. • Press the ON/OFF key in to turn on boiler (see fig. 1).
If the problem remains after two attempts at resetting, contact the Ferroli Service Centre. For other faults, refer to section 3.4 “Troubleshooting.” Before calling the Ferroli service centre, check that the problem is not due to an installation error or a problem with the gas/electricity or low water pressure in the system.
Maxima 35 C 2. INSTALLATION 2.1 General Instructions This device must only be used for the purpose for which it is specially designed. This unit is designed to heat water to a temperature below boiling point and must be connected to a hea- ting system and/or a water supply system for domestic use, compatible with its performance, characteristics and its heating capacity.
Maxima 35 C 2.2 Boiler location The unit’s combustion circuit is sealed off from the installation room. The installation room must be sufficiently well ventilated to prevent any dangerous conditions from forming in the event of even slight gas leakage. This safety standard is required by the EEC Directive no. 90/396 for all gas units, including those with a so-called sealed chamber.
Page 11
Maxima 35 C Make Up Water Provision must be made for replacing water lost from the sealed system. Reference should be made to BS6798, for methods of filling and making up sealed systems. There must be no direct connection between the boiler's central heating system and the mains water supply. The use of mains water to charge and pressurise the system directly, is conditional upon the Local Water Byelaws.
Maxima 35 C 2.3 Boiler water connections The heating capacity of the unit should be previously established by calculating the building’s heat requirement according to current regulations. For good operation and long life of the boiler, the plumbing system must be well proportioned and always complete with all those accessories that guarantee regular operation and running, room thermostat, trv’s and automatic bypass.
Ø22 fig. 6 Water treatment When treatment is used ferroli limited only recommend the use of proprietary Brand, such as Fernox or Sentinel water treatment products, which must be used in accordance with the manufactures instructions. for further information contact: Feronx Manufacturing Co.
Maxima 35 C 2.4 Connection to the gas system If necessary the local Gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas. An existing service pipe must not be used whitout prior consultation with the local Gas supplier.
Maxima 35 C Access to the electrical terminal board Follow the instructions given in fig. 7 to access the electrical connection terminal board (A fig. 7). The layout of the terminals for the various connections is given in the wiring diagram in the Technical Data chapter.
Page 16
Maxima 35 C External sensor (optional) Connect the sensor to its respective terminals 8 and 9 in appliance terminal block. The maximum per- missible length of the electric cable connecting the boiler - external sensor is 50 m. A common 2-wire cable can be used.
The current standards and local regulations must be observed. It should be notes that only Ferroli flue system and accessories should be used on this appliance, as per BS 5440 2000 and C.E. test certification.
Page 18
Maxima 35 C Connection with concentric fl ue system The unit can be connected to a concentric air/flue duct with a wall or rooftop outlet as shown on the following drawings. Numerous accessories are available on request to meet the various installation requirements.
Page 19
Maxima 35 C 4. If necessary, cut the end pipe to size, ensuring that the external pipe protrudes from the wall by between 10 and 60 mm (Fig. 9a and 9b). Remove the cutting burrs. 5. Connect the flue to the boiler, positioning the seals correctly. Seal the flue into the wall with silicone or sand + cement and cover with wall seals provided.
Page 20
3. Check that the total calculated loss is less than or equal to 55 equivalent metres, i.e. the maximum permissible for this model of boiler. For complete flue options please con- tact FERROLI or check our comprensive flue manual. Table 3 Equivalent Ref.
KWMA83W • 1,00 m KWMA85A Bend 45° Ø 80 mm male - female Vertical flue terminal KWMA65W KWMA84U Bend 90° Ø 80 mm male - female The stated loss values refer to genuine Ferroli fl ue accessories. KWMA01W Terminal Position D, E...
Page 22
Maxima 35 C Minimum Dimensions of Flue Terminal Positions Directly below an opening, air brick, 300mm opening windows, etc. Above an opening, air brick, 300mm opening windows, etc. Horizontally to an opening, air brick, 300mm opening windows, etc. 75mm Below gutters, soil pipes or drain pipes...
Connection to collective fl ues or single fl ues with natural draught If you are then going to connect the Maxima 35 C boiler to a collective flue or a single flue with natural draught, the flue must be expressly designed by professionally qualified technical personnel in conformity with the standards and rules in force.
Page 24
Maxima 35 C Condensate discharge Where possible the condensate should discharge into an internal soil pipe or waste system. The minimum pipe diameter required is 22 mm, a trap has already been fitted to the appliance with a flexible tail to facilitate the connection to the condensate discharge pipe.
All adjustment and conversion operations must be carried out by Qualified Personnel such as the Ferroli Technical Service. FERROLI declines any responsibility for damage or physical injury caused by unqualified and unauthorized persons tampering with the device. Gas supply conversion...
Maxima 35 C • Make sure that the unit is connected to a good earthing system. • Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler. • Vent and spin pumps. • Ensure flue system is correctly fitted, including terminal locations.
Page 27
Maxima 35 C Opening the casing To open the boiler casing, you need to follow the sequence given below and the instructions of fig. 15. 1 Using a screwdriver, fully unscrew the 2 screws “A ” 2 Open by pulling the panel “B ”...
Maxima 35 C 3.4 Troubleshooting Fault Diagnosis In the event of operating problems or a fault, the display will flash and a fault identification code appears. Faults marked with the letter “F” cause temporary shutdowns that are automatically reset as soon as the value comes back within the boiler’s normal working range.
Page 29
Maxima 35 C Fault Possible cause Cure Software fault • Software operating fault • Cut off and restore the electricity supply. If the trouble remains, check and/or change the main P.C.B. Flame absence after ignition • Ionization electode fault • Check ionization electrode position...
Maxima 35 C 4 TECHNICAL CHARACTERISTICS AND DATA 4.1 Dimensions and connections Top view System flow (22 mm with isolation valve fitted) DHW outlet (15 mm with isolation valve fitted) Gas inlet (22 mm with isolation valve fitted) Cold main inlet (15 mm with isolation...
Maxima 35 C 4.2 General view and main components Combustion chamber Gas inlet DHW outlet Cold water inlet CH flow CH return Safety valve Premix fan Combustion chamber Gas injector Ceramic burner Flue outlet manifold Heating pump Heating flow sensor...
Heating system connections Ø22 Hot water circuit connections Ø15 Maximum length of separate flues D=80* (*Measurement given in equivalent linear metres – cfr FERROLI calculation system) Electrical power supply Max electrical power absorbed Electric power drawn by the circulator (Speed I-II-III) 45-70-95...
Maxima 35 C 4.5 Diagrams Head available for the system QH Chart H [m] Q [m fig. 20 1 - 2 - 3 = Pump selector positions (Ferroli 15/60) A = Boiler losses of head...
2 6 7 BENCHMARK BENCHMARK No. Please add the first 4 digits of the Boiler serial No to complete the BENCHMARK No. GAS BOILER COMMISSIONING CHECKLIST C O L L E C T I V E M A R K BOILER SERIAL No.
SIGNATURE SERVICE 10 SERVICE 9 DATE DATE ENGINEER NAME ENGINEER NAME COMPANY NAME COMPANY NAME TEL No. TEL No. CORGI ID CARD SERIAL No. CORGI ID CARD SERIAL No. COMMENTS COMMENTS SIGNATURE SIGNATURE FERROLI TECHNICAL HELPLINE - 08707 282 885...
Page 40
Should you require help with any diffi culties call our Technical Service Helpline on 08707 282 885 Phone numbers: Installer Service Engineer BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS. ALL SPECIFICATIONS SUBJECT TO CHANGE Please note - to avoid incurring unnecessary expense, in the event of a boiler shut down, check this in not caused by lack of electricity supply, gas supply or low water pressure before calling our Customer Service Helpline.