GE LP 33 Series Operating Manual page 48

10 – 20 – 30 kva 400 vac ce / series 4
Hide thumbs Also See for LP 33 Series:
Table of Contents

Advertisement

4602
OPEN
4603
CLOSED
BATTERY TEST
4699
IMPOSSIBLE
REMOTE CONTROL
4763
REMOTE CONTROL
4764
OFF
Modifications reserved
OPM_LPS_33E_10K_30K_4GB_V030.doc
Q1
The auxiliary contact indicates that the output switch Q1 has
been opened.
Q1
The auxiliary contact indicates that the output switch Q1 has
been closed.
Not possible to start battery test (it is postponed) for:
No mains rectifier or bypass
-
Battery not fully charged
-
Load is below 10% or above 80%
-
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value of
respective parameter (password required):
ON
0 = Only local panel
1 = Only serial port on CI (TLC)
2 = Both
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value of
respective parameter (password required):
0 = Only local panel
1 = Only serial port on CI (TLC)
2 = Both
Page 48/85
Operating Manual LP 33 Series / 10-20-30 kVA