4.7.3
Input / output cable ratings
Cables size indicated below do not consider a possible line voltage.
NOTE !
The values given in the tables below do correspond to European Standards (EN) and,
in brackets, for Swiss standards (SEV/ASE).
In any case the local standards must be respected.
Fig. 4.7.3-1 Common input mains
UPS model
LP 33 Series / 10 kVA
LP 33 Series / 20 kVA 5 x 10 (5 x 16)
LP 33 Series / 30 kVA 5 x 10 (5 x 16)
NOTE !
According to EMC standards, the connection between the UPS and an external
battery must be done using a shielded cable!
Modifications reserved
OPM_LPS_33E_10K_30K_4GB_V030.doc
Recommended sizing for the lines A, B, C, D, E (mm
According to European Standards EN and Swiss standard SEV/ASE (in brackets)
A and B
C
5 x 4 (5 x 6)
5 x 4 (5 x 6)
5 x 10 (5 x 16)
5 x 10 (5 x 16)
Fig. 4.7.3-2 Separate input mains (option)
D
4 x 2.5 (4 x 4)
5 x 2.5 (5 x 4)
4 x 6 (4 x 10)
5 x 6 (5 x 10)
4 x 10 (4 x 16)
5 x 10 (5 x 16)
)
2
E
K
4 x 2.5 (4 x 4)
4 x 6 (4 x 10)
4 x 10 (4 x 16)
Page 30/85
Operating Manual LP 33 Series / 10-20-30 kVA