GE LP 33 Series Operating Manual page 56

10 – 20 – 30 kva 400 vac ce / series 4
Hide thumbs Also See for LP 33 Series:
Table of Contents

Advertisement

4.
Switch On the output switch Q1 (Pos. I).
The output will be supplied by the mains through the bypass.
Verify, selecting the screen METERING/Udcp and Udcn, that
the booster voltage has reached about 400 VDC.
5.
Switch On the inverter entering the screen:
MENU/COMMAND MENU/INVERTER ON
Some seconds later the load will be transferred on inverter
and the main screen will display: APPLICATION ON UPS
6.
Operation mode selection.
LP 33 Series is delivered normally selected for permanent VFI operation.
ECO Mode can be enabled and the ECO Mode START time & ECO Mode STOP time can be
programmed for each day of the week (see Section 7.3.1-5).
NOTE !
Even if the UPS is delivered with the battery fully charged, they could be partially
discharged during transportation or storage.
It is recommended to recharge the battery during a few hours in order to provide the
complete battery energy stored to the load in the event of mains failure.
Modifications reserved
OPM_LPS_33E_10K_30K_4GB_V030.doc
END OF PROCEDURE
LP 33
20kVA
APPLICAT. ON UTILITY
= 70%
Udcp=400V
Udcn=400V
Ubp=273V
Ubn=273V F
Charge level
= 100%
Autonomy
= 999min
COMMAND MENU
INVERTER ON
INVERTER OFF
LP 33
20kVA
APPLICATION ON UPS
= 70%
Operating Manual LP 33 Series / 10-20-30 kVA
*