2.
d1 ÷ d7:
Enabling time in function of weekdays.
For the weekdays from d1 to d7 (Saturday to Friday) the edit mode (edit day) allows to define time
intervals when the UPS is operating in ECO Mode.
The hour is given in 24-hour format.
These intervals are defined by:
ECO START:
ECO STOP:
The ECO Mode is enabled starting from the preceding ECO START time (the ECO START time of the
same day if this is earlier than the ECO STOP time, the ECO START time of the previous day
otherwise).
Identical times for ECO START and ECO STOP mantain the existing mode only in case the previous
command was ECO START and the following command will be ECO STOP.
3.
HOURS SELECTED:
To better understand the ECO Mode programming modes, some typical examples are shown:
Example 1:
For continuous ECO Mode set the ECO START times to 00:00 and the ECO STOP times to
23:59 for all weekdays, but almost 1 day must have 1 minute of VFI programmation: i.e
d2 - Sunday 00:00 to 23:58).
Weekday
d1
- Saturday
ECO START
00:00
ECO STOP
23:59
Example 2:
ECO STOP before ECO START.
ECO START 18:00, ECO STOP 06:00 for weekday d4 - Tuesday.
Means that on d4 - Tuesday the ECO Mode is active between 00:00 and 06:00 and
between 18:00 and 23:59.
Weekday
d1
- Saturday
ECO START
00:00
ECO STOP
23:59
Example 3:
ECO Mode during the night and week-end.
If the ECO Mode must be enabled all nights (d3 - Monday ÷ d7 - Friday) between 18:00 in
the evening and 06:00 of the following morning and during all Saturday (d1) and Sunday
(d2), the corresponding parameters are:
Weekday
d1
- Saturday
ECO START
00:00
ECO STOP
23:59
Modifications reserved
OPM_LPS_33E_10K_30K_4GB_V030.doc
the hour of the day after which the ECO Mode is enabled.
The ECO Mode is enabled until the following ECO STOP time is reached (the ECO
STOP time of the same day if this is later than the ECO START time, the ECO
STOP time of the following day otherwise).
the hour of the day before which the ECO Mode is enabled.
The number of ECO Mode hours per weekday (from d1 - Saturday to d7 -
Friday) is displayed in the operation mode parameter window (ceiling value).
d2
d3
- Sunday
- Monday
00:00
00:00
23:58
23:59
d2
d3
- Sunday
- Monday
00:00
00:00
23:59
23:59
d2
d3
- Sunday
- Monday
00:00
18:00
23:59
06:00
d4
d5
- Tuesday
- Wednesday
00:00
00:00
23:59
23:59
d4
d5
- Tuesday
- Wednesday
18:00
00:00
06:00
23:59
d4
d5
- Tuesday
- Wednesday
18:00
18:00
06:00
06:00
d6
d7
- Thursday
- Friday
00:00
00:00
23:59
23:59
d6
d7
- Thursday
- Friday
00:00
00:00
23:59
23:59
d6
d7
- Thursday
- Friday
18:00
18:00
06:00
06:00