Important Safety Rules - GE LP 33 Series Operating Manual

10 – 20 – 30 kva 400 vac ce / series 4
Hide thumbs Also See for LP 33 Series:
Table of Contents

Advertisement

1.1

IMPORTANT SAFETY RULES

GENERAL
Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
Check for sufficient floor and elevator loading capacity.
Check carefully the integrity of the UPS equipment.
In case you note some visible damage, do not put the UPS under voltage, but contact the nearest
Service Centre.
WARNING: RISK OF ELECTRICAL SHOCK.
Apart the front hinged lockable doors, do not remove any covers, there are no user serviceable
parts inside.
After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high
voltage remains at the terminals of the electrolytic capacitors.
All maintenance and service work should be performed by qualified service personnel.
The outlet-bars may be electrically live, even when the UPS is disconnected from the mains.
Dangerous voltages may be present during battery operation.
The battery protections must be removed before any maintenance or service work.
Be aware that the inverter can restart automatically after the utility voltage is restored.
INSTALLATION
This UPS must be installed and connected only by trained personnel.
Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
After removing the sidewalls of the UPS, make sure that all earth connections when reassembling,
are correctly reattached.
This UPS is intended for use in a controlled indoor environment free of conductive contaminants
and protected against animals intrusion.
High earth leakage current: Earth connection essential before connecting to AC input.
Switching OFF the unit does not isolate the UPS from the mains.
Do not install the UPS in an excessively humid environment or near water.
Avoid spilling liquids on or dropping any foreign object into the UPS.
The unit must be placed in a sufficiently ventilated area; the ambient temperature should not
exceed 35°C (95°F).
Optimal battery life is obtained if the ambient temperature does not exceed 25°C (77°F).
It is important that air can move freely around and through the unit.
Do not block the air vents.
Avoid locations in direct sunlight or near heat sources.
Modifications reserved
OPM_LPS_33E_10K_30K_4GB_V030.doc
Page 7/85
Operating Manual LP 33 Series / 10-20-30 kVA