4.7.2
Fuse ratings
Fig. 4.7.2-1 Mains input and battery fuses
UPS model
LP 33 Series / 10 kVA
LP 33 Series / 20 kVA
LP 33 Series / 30 kVA
Required protective devices
If ELCB breakers are prescribed to protect the input connections, consider the high leakage current
towards the earth generated by the noise-suppressor capacitors.
If strongly prescribed, the ELCB breakers should be the largest type suitable for non-linear current and
for delayed operation.
Fig. 4.7.2-2 Common input mains
UPS model
LP 33 Series / 10 kVA
LP 33 Series / 20 kVA
LP 33 Series / 30 kVA
Modifications reserved
OPM_LPS_33E_10K_30K_4GB_V030.doc
Fuses type URD 660/690V
F1 - F2 - F3
20 A (14 x 51)
40 A (14 x 51)
63 A (22 x 58)
Fuses (gL) or Circuit Breakers rating
for AC input 3x380/220V, 3x400/230V, 3x415/240V
F1
F2
3 x 25 A
3 x 25 A
3 x 50 A
3 x 50 A
3 x 63 A
3 x 63 A
LP 33 Series fuses
The UPS is equipped with rectifier input fuses F1,
F2, F3 and battery fuses F9, F10, F11.
In case of replacement the same type and the
same rating must be used (see table below).
Fuses type gG-gL 660/690V
Fig. 4.7.3- Separated input mains (option)
F3
3 x 20 A
3 x 35 A
3 x 50 A
F9 - F10 - F11
25 A (14 x 51)
50 A (14 x 51)
80 A (22 x 58)
F4 (external battery)
2 x 25 A
2 x 50 A
2 x 80 A
Page 29/85
Operating Manual LP 33 Series / 10-20-30 kVA