About OutBack Power Technologies OutBack Power Technologies is a leader in advanced energy conversion technology. OutBack products include true sine wave inverter/chargers, maximum power point tracking charge controllers, and system communication components, as well as circuit breakers, batteries, accessories, and assembled systems. Grid/Hybrid™...
Battery-to-AC inverting which delivers split-phase power (100/200 Vac to 120/240 Vac at 60 or 50 Hz) Model GS8048A can continuously produce 8 kVA (33 Aac) Model GS4048A can continuously produce 4 kVA (16 Aac) Mounts easily with supplied mounting plate ...
Introduction Components and Accessories IMPORTANT: This product is not compatible with the OutBack MATE or MATE2 System Display and Controller. Use of these products is not supported with the Radian Series. IMPORTANT: This product is not stackable with the GS8048 inverter. See page 32. Table 1 Components and Accessories Included in Box...
Planning Applications The Radian Series Inverter/Charger is intended for both off-grid and grid-interactive (Grid/Hybrid) applications. It is designed to use a battery bank to store energy. It can work in conjunction with photovoltaic (PV) modules to harvest solar energy, as well as wind turbines and other renewable sources.
Planning Input Modes The Radian inverter has seven modes of operation. These modes determine how the Radian interacts with an AC source. Each mode has functions and priorities that are intended for a designated application. Each of the Radian’s two AC inputs can be set to a different operating mode, so that different applications can be supported.
Planning Battery Bank When planning a battery bank, consider the following: Cables: Recommendations for battery cable size and length are shown on page 20. The maximum length will determine the placement of the battery bank. Other local codes or regulations may apply and may take priority over OutBack recommendations.
Planning Table 2 Battery Bank Elements G. System DC voltage: The Radian inverter Item Source of information requires nominal 48 Vdc to operate. A. Load Size Site-specific H. Battery voltage: Most individual battery B. Daily Hours Site-specific voltages are less than the system DC voltage. C.
Planning EXAMPLE #2 A. Backup loads: 1.75 kW (1750 W) 1) A ÷ [E x F] 1750 ÷ (0.97 x 0.93) = 1939.9 W Hours of use: 8 2) 1 ÷ G 1939.9 ÷ 48 = 40.4 Adc C. Days of autonomy: 2 3) 2 x B 40.4 x 8 = 323.3 Ahr D.
Planning Maintenance Bypass Switching Inverter systems are often equipped with AC maintenance bypass switches or interlocks. If the inverter system ever needs to be shut down or removed, the AC sources and loads must be disconnected. A bypass device allows the AC source to deliver power directly to the loads, bypassing the inverter.
Installation Location and Environmental Requirements Radian Series Inverter/Chargers must be located in a weather-proof enclosure or enclosed area. It is not designed for exposure to water or excessive wind-blown dust and debris. It carries an Ingress Protection (IP) rating of 20 and a Relative Humidity (RH) rating of 93%. The Radian inverter must be wall-mounted in an upright position.
Installation Tools Required The following tools may be required for this installation: Wrench and socket sets; should include torque and ratchet Insulated screwdriver set; should include wrenches; also reversible (stubby) wrenches for narrow access a #2 Phillips screwdriver 15 to16” long ...
Installation …continued from the previous page… Place the Radian inverter against the wall and slide it directly over the upper lip of the mounting plate. The inverter’s mounting flange should come to rest within the lip so that it hangs securely. Radian Inverter To assist in alignment, dimples have been placed on the side of the unit to mark the lower edge of the flange.
Installation Component Mounting The top of the GS Load Center (GSLC) connects to the bottom of the Radian inverter using four keyhole slots. The keyhole slots fit over four screws on the bottom of the inverter that secure the GSLC to the inverter when they are tightened. (The long screwdriver recommended on page 13 may be needed to reach these screws.) The GSLC should be secured to the wall using screws or wall anchors.
Installation Removing Front Cover The front cover must be removed in order to access the Radian inverter’s AC terminals and other connections. These include the Remote and Batt Temp ports, as well as several sets of auxiliary terminals. Twenty-two machine screws are located around the perimeter. Remove these screws with a #2 Phillips screwdriver.
Installation Terminals and Ports DC TERMINALS Connects to the battery cables and DC system. There are two DC positive and two DC negative terminals. Each DC positive terminal requires separate cables and separate overcurrent protection. See page 20 for instructions. RIBBON CABLES Connects the Radian’s power modules and control board.
Installation CONTROL WIRING TERMINAL BLOCK: Receives control wires for a variety of functions, including generator control. See facing page for terminal descriptions. REMOTE and BATTERY TEMP PORTS: Receive the RJ45 and RJ11 plugs from the MATE3 system display and Remote Temp Sensor.
Installation Wiring It will be necessary to remove knockouts from the chassis to run wires. Bushings are included with the hardware kit to protect the wires. Make sure to install these bushings in the holes. Use copper wire only. Wire must be rated at 75°C or higher. Grounding WARNING: Shock Hazard This unit meets the IEC requirements of Protection Class I.
(provided). Notes on assembly and cabling are shown on the next page. IMPORTANT: The Radian GS8048A contains two internal power modules, each with its own set of DC terminals. Both sets of terminals must be connected to battery power for the inverter to work correctly.
M8-1.25 Hex Bolt The hardware should be arranged according to the appropriate image below. GSLC models used with the GS8048A inverter are equipped with a DC positive (+) plate. The plate accepts an M8 hex bolt and nut. See image B.
Installation AC Wiring WARNING: Shock Hazard The neutral and ground conductors should be mechanically bonded. Ensure there is no more than one AC neutral-ground bond at any time. Local or national codes may require the bond to be made at the main panel only.
Page 25
Installation The terminals labeled L1 and L2 GRID are used to connect to the two utility grid “hot” wires. The L1 and L2 wires are usually black and red respectively, and read 120 Vac each when measured with respect to neutral. In a standard service, L1 and L2 are 180 degrees out of phase and should read 240 Vac when measured from one to the other.
Installation AC Sources The inverter’s transfer relay is normally set to provide inverter power to the output. The conditions for AC acceptance are defined by the inverter’s programmed settings and AC input mode. The relay will switch to transfer the AC source power to the output when the AC acceptance conditions are met.
Installation Accessory Wiring The upper board has ports for both the Remote Temperature Sensor (RTS) and the system display. The system display port is System Display port labeled Remote. The RTS port is labeled Battery Temp. If a HUB Communications Manager is in use, it RTS port occupies the inverter’s Remote port.
Installation AUX Wiring The Radian inverter has two sets of terminals which can respond to different criteria and control many functions. These include cooling fans, vent fans, load diversion, fault alarms, and the Advanced Generator Start (AGS) function. The 12V AUX terminals are a switched 12 Vdc power supply. They can control any of the Auxiliary Output functions available in the system display (MATE3).
Installation In this example, the 12V AUX terminals drive a relay that diverts wind power. The relay’s coil is connected to the 12V AUX terminals. When the AUX function closes the relay (based on battery Turbine voltage), the relay diverts the excess wind power to a water heating element.
Installation In other cases, or in the case of a three-wire-start generator, the inverter should use the 12V AUX terminals instead, in conjunction with a three-to-two wire converter. (See pages 28 and 29.) Two-Wire-Start Generator Starting Switch Figure 23 Two-Wire Generator Start (RELAY AUX) Two-Wire-Start (12V AUX Terminals) The 12 Vdc signal provided by the 12V AUX terminals can be switched on and off to provide a start signal.
Installation Three-Wire-Start A “three-wire-start” generator has two or more starting circuits. It usually has a separate switch or position for cranking the generator. A three-wire generator has fewer automated functions than a two-wire. It usually requires multiple controls for starting, running, or stopping. The inverter terminals cannot control this type of generator without using a three-wire to two-wire conversion kit.
Installation AC Configurations Single-Inverter Figure 26 (below) shows the general wiring of the Radian inverter and the AC system connected to it. This figure is not a physical representation of the inverter and does not depict the GSLC. Figure 27 (see next page) shows the locations of AC and network connections. This figure is a physical diagram for wiring the GSLC, network components, and external AC devices with the inverter.
Installation NOTES: 1. Ground wiring is not shown for reasons of simplicity. Regardless, this system must be connected to a grounded, permanent wiring system. See page 19. 2. The Radian inverter has separate neutral connections for grid input, generator input, and output. These are electrically common. If an external neutral bus exists (as shown in the GSLC), not all of the Radian neutral connections need to be made.
1 on the communications manager. In a parallel-stacked system, the master tends to be the most heavily used unit. Only one slave mode, “OutBack”, is available for the GS8048A and GS4048A. This mode is used for inverters stacked in parallel.
Page 36
Installation IMPORTANT: Neither the GS8048A nor the GS4048A can stack with the previous model GS8048. The GS8048 can share a HUB product with the others if it is wired independently. The GS8048A can be stacked with the GS4048A using HUB products. To optimize ...
Installation Parallel Stacking (Dual-Stack and Larger) In parallel stacking, two or more inverters are stacked to create a single, common AC bus as shown in Figure 29. The slave outputs are controlled directly by the master and cannot operate independently. ...
Installation NOTES: 1. The Radian inverter has separate neutral connections for grid input, generator input, and output. These are electrically common. If an external neutral bus exists (as shown in the AC Load Panel above), not all of the Radian neutral connections need to be made. 2.
Installation NOTES: 1. Ground wiring is not shown for reasons of simplicity. Regardless, this system must be connected to a grounded, permanent wiring system. See page 19. 2. The Radian inverter has separate neutral connections for grid input, generator input, and output. These are electrically common. If an external neutral bus exists (as shown in the GSLC), not all of the Radian neutral connections need to be made.
Installation Functional Test Once the mounting, wiring, and other installation steps are completed, proceed to the Radian Series Inverter/Charger Operator’s Manual. The Operator’s Manual has steps for system commissioning. These include powering up and performing a functional test on the inverter system, as well as powering down and adding new devices to an existing system.
Symbols, Terms, and Definitions Symbols Used WARNING: Hazard to Human Life This type of notation indicates that the hazard could be harmful to human life. CAUTION: Hazard to Equipment This type of notation indicates that the hazard may cause damage to the equipment. IMPORTANT: This type of notation indicates that the information provided is important to the installation, operation and/or maintenance of the equipment.
Terms and Definitions Table 5 Terms and Definitions Term Definition Emergency Power Off; a switching product used for emergency shutdown GFDI Ground Fault Detector Interruptor; a safety device for PV systems Ground; a permanent conductive connection to earth for safety reasons; also known as Chassis Ground, Protective Earth, PE, Grounding Electrode Conductor, and GEC Grid/Hybrid™...
Page 46
THIS PAGE INTENTIONALLY LEFT BLANK. 900-0160-01-00 Rev A...
Page 47
THIS PAGE INTENTIONALLY LEFT BLANK. 900-0160-01-00 Rev A...
Page 48
Masters of the Off-Grid.™ First Choice for the New Grid. Corporate Headquarters European Office 17825 – 59 Avenue N.E. Hansastrasse 8 Suite B D-91126 Arlington, WA 98223 USA Schwabach, Germany +1.360.435.6030 +49.9122.79889.0 900-0160-01-00 Rev A...
Need help?
Do you have a question about the Radian GS8048A and is the answer not in the manual?
Questions and answers