Generator - OutBack Power Radian GS8048A Installation Manual

Radian series inverter/charger
Hide thumbs Also See for Radian GS8048A:
Table of Contents

Advertisement

EXAMPLE #2
A. Backup loads: 1.75 kW (1750 W)
B.
Hours of use: 8
C. Days of autonomy: 2
D. Off-grid system (GS4048A inverter)
E.
Conductor efficiency: 97% (0.97)
F.
Inverter efficiency: 93% (0.93)
G. System voltage: 48 Vdc
H. Batteries: OutBack EnergyCell 200RE (12 Vdc)
I.
Capacity at 8-hour rate: 167.5 Ahr
J.
Maximum DoD: 50% (0.5)

Generator

These Radian models can work with any "split-phase" generator that delivers reliable AC power at the
appropriate voltage and frequency. They cannot work with a single-phase or three-phase generator.
CAUTION: Equipment Damage
Use of a three-phase generator with this equipment may damage either the inverter or
the generator. This damage to the inverter is not covered by the product warranty.
 The Radian inverter/charger can provide a start signal to control an automatic start generator. If automatic
generator starting is required, the generator must be an electric-start model with automatic choke. It
should have two-wire start capability. For other configurations, additional equipment may be required.
 In any configuration, the inverter may need to be programmed using the system display.
Perform all programming according to the specifications of the generator and the required operation of the
inverter. Parameters to be programmed may include generator size, automatic starting requirements, and
potential fluctuations in generator AC voltage.
Generator Sizing
A generator should be sized to provide enough power for all the loads and the battery charger.
 Available generator power may be limited by ratings for circuit breakers and/or generator connectors.
The maximum allowed AC circuit breaker size is 50 Aac per Radian inverter/charger.
 The generator must be able to provide current to all inverters. Minimum generator wattage
recommended to be twice the wattage of the inverter system. Many generators may not be able to
maintain AC voltage or frequency for long periods of time if they are loaded more than 80% of
rated capacity.
A generator that is to be installed in a building usually should not have a bond between the neutral and
ground connections. The generator should only be bonded if there is a specific need. Installations in North
America are expected to bond the neutral and ground at the main electrical panel. See page 22 for more
information on neutral-ground bonding.
This is the wattage value after deratings for the following: peak versus continuous power, load power factor considerations,
1
fuel type, altitude, and ambient temperature.
900-0160-01-00 Rev A
1) A ÷ [E x F]
1750 ÷ (0.97 x 0.93) = 1939.9 W
2) 1 ÷ G
1939.9 ÷ 48 = 40.4 Adc
3) 2 x B
40.4 x 8 = 323.3 Ahr
4) [3 x C] ÷ J
[323.3 x 2] ÷ 0.5 = 1293.3 Ahr
5) 4 ÷ I
1293.3 ÷ 167.5 = 7.7 (rounded to 8)
6) [G ÷ H] x 5
[48 ÷ 12] x 8 strings = 32 batteries
Planning
is usually
1
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Radian gs4048a

Table of Contents