OutBack Power RADIAN Series Quick Start Manual

OutBack Power RADIAN Series Quick Start Manual

Inverter/charger
Hide thumbs Also See for RADIAN Series:

Advertisement

Quick Links

Setup and Programming
CAUTION: Equipment Damage
!
These procedures should be done by a qualified installer who is trained on programming inverter power systems.
Failure to set accurate parameters for the system could potentially cause equipment damage. Damage caused by
inaccurate programming is not covered by the limited warranty for the system.
IMPORTANT
Check the firmware revision of all OutBack devices before use. The Radian inverter and MATE3 system display may not
communicate or operate correctly unless their firmware is above a specified revision number.
For models GS8048A and GS4048A, the firmware must be revision 001.005.xxx or higher.
The MATE3 must be revision 002.017.xxx or higher.
Configuration Wizard
The MATE3 Configuration
Settings
Wizard allows quick setup of
Configuration Wizard
Configuration Wizard
Device Data Logs
parameters that apply to all
Event Logs
Firmware Update
systems. The Configuration
Wizard is reached from the
MATE3 Main Menu as shown
New Configuration
New Configuration
to the right.
Existing Configuration
Restore Configuration
New Configuration Initialized
The firmware revision of all
devices can be confirmed by
Back
Continue
navigating from the MATE3
Main Menu as shown below.
Upgrades to the firmware
Off Grid
revision can be downloaded
from the OutBack website
System Type
Off Grid
www.outbackpower.com.
System Voltage
48 VDC
Array Wattage
1000
Battery Type
FLA
Capacity
Firmware Revision
Back
Absorb Voltage
57.6 VDC
Settings
>>
Float Voltage
54.4 VDC
Configuration Wizard
Settings
>>
Equalize Voltage
60.0 VDC
Device Data Logs
>>
Re-Float Voltage
44.0 VDC
Event Logs
>>
Firmware Update
>>
Back
AC Output Voltage 240 VAC
System
System
>>
AC Phase
Single
Inverter
>>
AC Input Breaker Size 50 A
Charge Controller
>>
Maximum Output Load
33 A
Battery Monitor
>>
MATE3
>>
Back
Generator Installed
Y
System Information
>>
Generator Type
AC
Save / Store Information
>>
Generator Start
Manual
Firmware Version
>>
AUX Output Device Port 1
Date and Time
>>
LCD Display
>>
Back
Note: See the MATE3
manual for details on
MATE3
002.017.018
generator control.
1:
GS8048A 001.005.002
2:
GS8048A 001.005.002
If FN-DC is installed...
Shunt A
Connection
Inverter
S
This advances the display to the
Setup Complete screen.
Back
C
This advances the display to the
Setup Complete screen if the
Shunt B
Connection
Charge Controller
FLEXnet DC is not installed. If the
FLEXnet DC is installed, the display
Back
advances to the Shunt screens.
Shunt C
Connection
Charge Controller
Back
900-0162-01-00 Rev A.vsd\Page-1\2014-01-24
©2014 OutBack Power Technologies. All Rights Reserved.
>>
>>
Grid Tied
Backup
>>
>>
>>
System Type
Grid Tied
System Type
System Voltage
48 VDC
System Voltage
Array Wattage
1000
Array Wattage
Battery Type
FLA
Capacity
500 Ah
Battery Type
>>
Back
Continue
Back
>>
>>
Absorb Voltage
57.6 VDC
Time 1.0
Absorb Voltage
Float Voltage
54.4 VDC
Time 1.0
Float Voltage
Equalize Voltage 60.0 VDC
Time 3.0
Equalize Voltage
Re-Float Voltage 44.0 VDC
Re-Float Voltage
Back
Continue
Back
AC Output Voltage 240 VAC
AC Output Voltage 240 VAC
AC Phase
Single
AC Phase
AC Input Breaker Size 50 A
AC Input Breaker Size 50 A
Maximum Output Load
33 A
Maximum Output Load
Back
Continue
Back
Generator Installed
N
Generator Installed
Generator Type
AC
Size
5.0 kW
Generator Type
Generator Start
Manual
Generator Start
AUX Output Device Port 1
AUX Output Device Port 1
Back
Continue
Back
500 Ah
Continue
Period 1 Enable
N
Weekday Use
0:00
Drop 0:00
Weekend Use
0:00
Drop 0:00
Time
1.0
Time
1.0
Back
Continue
Back
Time
3.0
Continue
Period 2 Enable
N
Weekday Use
0:00
Drop 0:00
Back
Continue
Back
Continue
Period 3 Enable N
Weekday Use
0:00
Drop 0:00
Size
5.0 kW
Back
Back
Continue
Continue
C
Mode Disabled
Mode Disabled
Grid Connect
48.0 VDC
Delay 60 Min
Grid Connect
Grid Disconnect
52.0 VDC
Delay 60 Min
Grid Disconnect
Grid Connect SOC 60%
Disconnect SOC 95%
Grid Connect SOC 60%
Back
Continue
Back
C
If FN-DC is installed...
If FN-DC is installed...
Shunt A
Connection
Inverter
Back
Continue
Back
Continue
Shunt B
Connection
Charge Controller
Continue
Back
Continue
Back
Shunt C
Connection
Charge Controller
Back
Continue
Back
Continue
S
S
Quick Start Guide
WARNING: Fire/Explosion Hazard
Do not place combustible or flammable materials within 12 feet (3.7 m) of
the equipment. This unit employs mechanical relays and is not ignition-
protected. Fumes or spills from flammable materials could be ignited by sparks.
WARNING: Personal Injury
Use safe lifting techniques and standard safety equipment when working with
this equipment.
IMPORTANT:
Clearance and access requirements may vary by location. Maintaining a 36"
(91.4 cm) clear space in front of the system for access is recommended.
Consult local electric code to confirm clearance and access requirements
for the specific location.
Backup
48 VDC
1000
FLA
Capacity
500 Ah
Continue
57.6 VDC
Time
1.0
54.4 VDC
Time
1.0
60.0 VDC
Time
3.0
44.0 VDC
MATE3
Continue
System
Display and
Controller
Single
33 A
Continue
N
AC
Size
5.0 kW
Manual
Continue
Period 1 Enable
N
Weekday Use 0:00
Drop 0:00
Weekend Use 0:00
Drop 0:00
Continue
Period 2 Enable
N
Weekday Use 0:00
Drop 0:00
Continue
Period 3 Enable
N
Weekday Use 0:00
Drop 0:00
Continue
HUB 10.3
48.0 VDC
Delay 60 Min
52.0 VDC
Delay 60 Min
Communications
Disconnect SOC 95%
Continue
Manager
C
Shunt A
Connection
Inverter
Continue
GS Load Center
(GSLC)
Shunt B
Connection
Charge Controller
Continue
Contact Technical Support:
Shunt C
Telephone:
+1.360.618.4363
Connection
Charge Controller
Email:
Support@outbackpower.com
Continue
Website:
www.outbackpower.com
S
Radian Inverter/Charger
FM80 Charge
Controllers
(x2)
RADIAN Series
Major Components
Radian System Products
GS8048A
Inverter/Charger
GS4048A
GSLC175-PV-120/240
GS Load Center
GSLC175PV1-120/240
(both depicted)
MATE3 depicted
System Display
(with FW-MB3
and Controller
mounting bracket)
Optional OutBack Components
Communications
HUB10.3 depicted
Manager
FLEXmax 80 depicted
Charge Controller
(with FW-CCB2
mounting bracket)
PV Combiner Box
PV12 depicted
Remote Temperature Sensor (RTS)
FLEXnet DC Monitor (FN-DC)
Battery Bank
EnergyCell depicted
Customer-Supplied Components
Utility Grid or
AC Source
AC Generator
Main Electrical Panel (or overcurrent
device for the AC source)
Electrical Distribution Subpanel
(Load Panel)
Photovoltaic (PV) Array
IMPORTANT:
Not intended for use with
life support equipment.
Masters of the Off-Grid.™
First Choice for the New Grid.

Advertisement

loading

Summary of Contents for OutBack Power RADIAN Series

  • Page 1 +1.360.618.4363 Connection Charge Controller Connection Charge Controller Connection Charge Controller Email: Support@outbackpower.com Masters of the Off-Grid.™ Back Continue Back Continue Back Continue 900-0162-01-00 Rev A.vsd\Page-1\2014-01-24 Website: www.outbackpower.com First Choice for the New Grid. ©2014 OutBack Power Technologies. All Rights Reserved.
  • Page 2 Lock Washer Positive (+) also has one location. Washer or destroy the equipment Shunt Sense Terminal L1 L2 L1 L2 L1 L2 and void the product 900-0162-01-00 Rev A.vsd\Page-2\2014-01-24 GRID ©2014 OutBack Power Technologies. All Rights Reserved. warranty. GSLC175-PV-120/240 GSLC175PV1-120/240...
  • Page 3 18. Turn on the AC disconnects at the backup (or critical) load panel and test the loads. Verify 0 Vac on the AC output circuit breakers by placing the voltmeter connections at the source. leads on . Repeat this step for 900-0162-01-00 Rev A.vsd\Page-3\2014-01-24 ©2014 OutBack Power Technologies. All Rights Reserved.
  • Page 4 PV Array #2 PV Array #1 CAT5 Cable AC Generator Generator Start Battery Bank AC Subpanel BATTERY LEGEND LEGEND Negative Negative Loads Positive Positive GROUND Vented Battery Enclosure Ground Ground 900-0162-01-00 Rev A.vsd\Page 4\2014-01-24 ©2014 OutBack Power Technologies. All Rights Reserved.