1.6 Specifications

The UPS specifications are listed in Table 1-2.
Product model
Input
Output
Battery
Recharge duration (standard
Transfer time
Noise (within 1m)
EMC
Surge protection
Protection level
Environmental
condition
Size
Weight
Rated voltage
Voltage range
Frequency
Power factor
Rated power
Voltage
Frequency
Slew rate
Power factor
Crest factor
Voltage harmonic distortion
Load regulation rate
Dynamic response recovery
time
Overload capacity
Bypass voltage
Mains efficiency
Type
Cell No.
Rated voltage
UPS)
Charge current
Normal←→Battery
Inverter←→Bypass
Display
Safety
Conduction emission
Immunity
Harmonic current
Operating temperature
Storage temperature
Relative humidity
Altitude
W × H × D (mm)
Standard UPS (kg)
Extended UPS (kg)
iTrust Adapt 6kVA UPS User Manual
Table 1-2 UPS specifications
Standard UPS
UHA1R-0050
Single-phase: 220Vac, 3-phase: 380Vac
176Vac ~ 276Vac, at full load
120Vac ~ 160Vac, linear derating
120Vac, at half load
50Hz ± 5Hz
Single-phase: ≥ 0.99, 3-phase: ≥ 0.95
6kVA/4.2kW
220Vac ± 3%
In Normal mode: synchronizes with the bypass frequency when the bypass
frequency is within 50Hz ± 5Hz
In Battery mode is 50Hz ± 0.2Hz
Bypass frequency track range is ±10%
0.2Hz/s (default), 1Hz/s
0.7 (6kVA)
3:1
≤ 3% (linear load), ≤ 5% (non-linear load)
2%
60ms
105% ~ 125% rated load for 1min, 125% ~ 150% rated load for 100ms
120Vac ~ 253Vac
91%
Sealed, lead-acid, maintenance-free battery (12V/7Ah)
16
192Vdc
Fours hours to 90% rated capacity
2A
0
≤ 4ms
≤ 50dB
LED/LCD (optional)
CCEE (GB4943-1995)/GB4943
IEC/EN 62040-2
I ≤ 16A, IEC/EN61000-3-3; 16A < I ≤ 75A, IEC/EN61000-3-11
I ≤ 16A, IEC/EN61000-3-2; 16A < I ≤ 75A, IEC/EN61000-3-12
YD/T1095-2001 level 2 15%
IEC/EN-61000-4-5, endurance level 4 (4kV) (live line to earth), level 3 (2kV)
(during live lines)
IP20
0°C ~ +40°C
-40°C ~ +70°C (battery excluded); -20°C ~ +55°C (battery included)
5% ~ 95%, non-condensing
< 1500m, derating in accordance with GB/T3859.2 when higher than 1500m
430 × 88 × 630
23
25
Chapter 1 Product Description
Extended UPS
UHA1R-0050L
Depended on external battery capacity
4A
5