iTrust Adapt 6kVA UPS

User Manual

Version
V1.0
Revision date
BOM
Emerson Network Power provides customers with technical support. Users may
contact the nearest Emerson local sales office or service center.
Copyright © 2009 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change without
notice.

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Adapt

  • Page 1: User Manual

    Adapt 6kVA UPS User Manual Version V1.0 Revision date Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Copyright © 2009 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without...
  • Page 3 Safety Guidelines Prohibitions 1. Non-professionals are prohibited to install or commission the UPS alone. 2. As hazardous voltages are present within the UPS, only an Emerson technician or an Emerson-authorized technician is permitted to open it. Failure to observe this could result in electric shock risk and invalidation of any implied warranty.
  • Page 4 11. The UPS output cable must be less than 10m. Others When the UPS is purchased to deliver power to the equipment listed below, please discuss with the distributor in advance about the applicability, settings, management and maintenance of the UPS, as these need special considerations during design and development.
  • Page 5: Table Of Contents

    Contents Chapter 1 Product Description .......................... 1 1.1 Features.............................. 1 1.2 Model Configuration..........................1 1.3 Appearance And Components......................2 1.3.1 Appearance ..........................2 1.3.2 Components ..........................2 1.4 Operating Principle ..........................3 1.5 UPS State And Operation Mode ......................3 1.5.1 Normal Mode ...........................
  • Page 6 4.2 UPS Power-On ..........................19 4.3 Turning On UPS..........................19 4.4 Battery Self-Test ..........................20 4.4.1 Battery Power-On Self-Test....................20 4.4.2 Battery Manual Self-Test ....................... 20 4.4.3 Battery Periodic Self-Test ...................... 21 4.5 Turning Off UPS..........................21 4.6 UPS Power-Off ..........................22 4.7 Transferring UPS Between Operation Modes...................
  • Page 7: Chapter 1 Product Description

    Chapter 1 Product Description iTrust Adapt 6kVA UPS (UPS for short) is an intelligent online UPS system with sine wave output developed by Emerson Network Power Co., Ltd. The UPS provides reliable and high quality AC power to your sophisticated equipment.
  • Page 8: Appearance And Components

    Battery port Input switch Battery port 230/400Vac-40A 192Vdc 27A SNMP card solt (with I/O terminal block USB port Ventilation hole protective cover) (with protective cover) Figure 1-2 UPS rear panel iTrust Adapt 6kVA UPS User Manual...
  • Page 9: Operating Principle

    When the UPS is in Bypass mode, the BYPASS indicator is on. Note In the event of a mains failure or mains voltage outside the specifications (120Vac ~ 253Vac) when the UPS is in Bypass mode, the UPS will cease power for the load. iTrust Adapt 6kVA UPS User Manual...
  • Page 10: Battery Mode

    However, if the bypass fails or bypass voltage is abnormal when the output IS overloaded, the UPS will not switch to the inverter, but shut down the bypass. iTrust Adapt 6kVA UPS User Manual...
  • Page 11: Specifications

    5% ~ 95%, non-condensing Altitude < 1500m, derating in accordance with GB/T3859.2 when higher than 1500m Size W × H × D (mm) 430 × 88 × 630 Standard UPS (kg) Weight Extended UPS (kg) iTrust Adapt 6kVA UPS User Manual...
  • Page 12: Chapter 2 Installation

    Small slotted screwdriver EJ375mm Connect input and output cables 2.3 Mechanical Installation Two installation modes are available: tower installation and rack installation. You can select an appropriate installation mode according to the actual conditions. iTrust Adapt 6kVA UPS User Manual...
  • Page 13: Tower Installation

    Figure 2-2 Installing support base with support base extension (front view) 3. Place the UPS on the support bases. Each UPS needs four support bases to install, as shown in Figure 2-3. Battery module Support base Support base Figure 2-3 Tower installation iTrust Adapt 6kVA UPS User Manual...
  • Page 14: Rack Installation

    The rack installation method of standard UPS with single UPS and single battery module is shown in Figure 2-6. Battery module Figure 2-6 Rack installation of standard UPS with single UPS and single battery module iTrust Adapt 6kVA UPS User Manual...
  • Page 15: Connecting Cables

    Adopt correct power distribution method to ensure safety of the UPS and loads. Correct power distribution method is shown in Figure 2-8. Input live line Output live line Load Output neutral Input neutral line line Quadrupole linkage breaker Figure 2-8 Correct power distribution method iTrust Adapt 6kVA UPS User Manual...
  • Page 16: Connecting Battery Cables

    3. Take out a battery cable from accessories of the battery module. Connect one end of battery cable to the battery port on the rear panel of the UPS, and connect the other end to any battery ports (two in all) on the rear panel of the battery module. iTrust Adapt 6kVA UPS User Manual...
  • Page 17: Connecting Communication Cables

    Through the optional SNMP card, users can access the UPS operation state and information using background monitoring software delivered with SNMP card. The installation and communication cable connection of the SNMP card are as follows: iTrust Adapt 6kVA UPS User Manual...
  • Page 18: N + 1 Parallel System (Optional)

    Connecting parallel cables Connecting POD cables 2.5.1 Mechanical Installation Taking rack UPS parallel system installation as an example, the installation method of the N+1 parallel system is as follows: Installing POD Installing UPS Installing battery module iTrust Adapt 6kVA UPS User Manual...
  • Page 19 Figure 2-15 Installation diagram of the 3+1 parallel system excluding battery module The installation diagram of the 3-phase input single-phase output 3 + 1 parallel system and single-phase input single-phase output 3 + 1 parallel system including battery module is shown in Figure 2-16. iTrust Adapt 6kVA UPS User Manual...
  • Page 20: Setting Parallel Addresses

    2. For single-phase input single-phase output 3 + 1 parallel system and 3-phase input single-phase output 3 + 1 parallel system, set the UPS according to Table 2-2. 3. Only Emerson-authorized technicians are allowed to operate DIP switch. Otherwise, the UPS may be damaged. iTrust Adapt 6kVA UPS User Manual...
  • Page 21: Connecting Parallel Cables

    Input -W AC INPUT W Output -PE AC OUTPUT PE Output -L AC OUTPUT Output -N AC OUTPUT Note When connecting cables, connect the UPS end at first, and then connect the POD end. iTrust Adapt 6kVA UPS User Manual...
  • Page 22 3. When you need to turn off the UPS in the parallel system, press the OFF key on the corresponding UPS firstly to cut off the output of the UPS, and then open the input and output MCBs of the corresponding POD. iTrust Adapt 6kVA UPS User Manual...
  • Page 23: Chapter 3 Operation And Display Panel

    Load state, battery remaining capacity display or fault orientation indicator, includes five indicators, of which four indictors are green and one indicator is yellow. The yellow indicator indicates UPS load over-capacity or battery capacity too-low. iTrust Adapt 6kVA UPS User Manual...
  • Page 24: Ups State Indicators

    : alarm; when the UPS is in the event of the normal mode, the UTILITY indicator and INVERTER indicator are on Note Indicator 5 is yellow, indicator 6 is red and other indicators are green. iTrust Adapt 6kVA UPS User Manual...
  • Page 25: Chapter 4 Operation Instructions

    After UPS power-up, press and hold the ON/SILENCE key for more than one second. After 30 seconds, the UPS will switch to mains inverter standby mode automatically and the INVERTER indicator will blink. When the UPS has output, the INVERTER indicator will turn on, as shown in Figure 4-2. iTrust Adapt 6kVA UPS User Manual...
  • Page 26: Battery Self-Test

    Battery manual self-test includes battery in-position test and battery state test. Press and hold the ON/SILENCE key for four seconds, the battery self-test will begin and the BATTERY indicator will turn on, under the precondition that: iTrust Adapt 6kVA UPS User Manual...
  • Page 27: Battery Periodic Self-Test

    At this point, the UPS is not powered off completely and the UTILITY indicator flashes, as shown in Figure 4-6. If you wish to power off the UPS completely, you need to open the mains switch. Figure 4-6 Indicator displaying during UPS turning off iTrust Adapt 6kVA UPS User Manual...
  • Page 28: Ups Power-Off

    UPS will be shut down automatically. When the mains is normal, the UPS restarts automatically and switches to Normal mode. This restarting function is designed for unattended operation. If the UPS is shut down manually during battery state operation, the UPS should be restarted manually when the mains resumes. iTrust Adapt 6kVA UPS User Manual...
  • Page 29: Transferring Ups From Inner Overheating Protection To Bypass Mode

    OFF key after ten seconds). After removing the shorting fault, the UPS can be re-connected to the mains and be restarted. 4.8 UPS Monitoring For UPS monitoring methods, refer to SiteMonitor software delivered with the UPS. iTrust Adapt 6kVA UPS User Manual...
  • Page 30: Chapter 5 Maintenance And Troubleshooting

    Battery mode, find out the reason, for instance: is it because of mains failure, battery test, operator intervention, and so on. 5.5 Checking UPS Functions Note UPS function check procedures may cause power interruption to load! iTrust Adapt 6kVA UPS User Manual...
  • Page 31: Troubleshooting

    4. Wait for ten minutes and restart the UPS The buzzer beeps for a long time, the Remove the output short circuit fault and FAULT indicator illuminates, and the UPS output short circuit restart the UPS LCD displays OUTPUT SHORT iTrust Adapt 6kVA UPS User Manual...
  • Page 32: Technical Support

    Your computer configuration, including operating system, revision level, expansion cards, and software. Any error messages displayed at the time the error occurred. The sequence of operations that led up to the error. Any other information you feel may be of help. iTrust Adapt 6kVA UPS User Manual...
  • Page 33: Appendix 1 Battery Module

    The battery module provides battery ports, battery fuse box and ventilation holes on the rear panel, as shown in Figure 2. Battery port 1 Battery port2 Ventilation holes Battery f use box Figure 2 Rear panel of the battery module iTrust Adapt 6kVA UPS User Manual...
  • Page 34 2. The length of the standard battery cable delivered with the battery module is 0.5m. If user needs more length cable, please consult the dealer. iTrust Adapt 6kVA UPS User Manual...
  • Page 35: Appendix 2 Communication Function

    Pin 6: connected to TX of the RS232 communication port of the host Pin 7: reserved Pin 8: card gating signal, connected to +9_TR after inserting SNMP card Pin 10: supplied by DSP plate, used to card gating iTrust Adapt 6kVA UPS User Manual...
  • Page 36: Appendix 3 Lcd Operation And Display Panel

    LCD Pressing and holding this key for less than one second opens the selected menu and confirming. Pressing and ENTER key holding this key for more than one second returns to previous menu iTrust Adapt 6kVA UPS User Manual...
  • Page 37: Lcd Operation And Display Interface

    Self-test cycle Disabled (default), 3-month, 6-month, 9-month, 12-month information Setting Installation mode Horizontal (default), vertical Language Chinese (default), English Resume Resume default default Return Inverter asynchrony Alarm Inverter failure message Rectifier failure Abnormal bus voltage iTrust Adapt 6kVA UPS User Manual...
  • Page 38 Pressing and holding this key for less than one second enters the selected menu. Pressing and holding this key ENTER key for more than one second returns to the parallel menu, there is no response when the UPS is single iTrust Adapt 6kVA UPS User Manual...
  • Page 39 LIE STAND YES, NO NO 3 6 9 12 LANGUAGE: UPS TYPE: 中文 English 5KVA 6KVA Setting interface 1 Setting interface 2 LCD setting interface Resume factory parameter interface Figure 11 Parameter setup interface iTrust Adapt 6kVA UPS User Manual...
  • Page 40 Pressing and holding this key for less than one second: no response. Pressing and holding this key for more CYCLE key than one second turns on/turns off the backlight on the LCD ENTER key Returns to the previous menu iTrust Adapt 6kVA UPS User Manual...
  • Page 41: Appendix 4 Pod

    2. Single-Phase Input Single-Phase Output 3 + 1 POD The appearance of the single-phase input single-phase output 3 + 1 POD is shown in Figure 16. Plastic panel Figure 16 Single-phase input single-phase output 3 + 1 POD iTrust Adapt 6kVA UPS User Manual...
  • Page 42: Phase Input Single-Phase Output 3 + 1 Pod

    UPS 3 output switch Figure 20 Operation panel of the 3-phase input single-phase output 3 + 1 POD The rear panel of the 3-phase input single-phase output 3 + 1 POD is shown in Figure 21. iTrust Adapt 6kVA UPS User Manual...
  • Page 43 UPS 2 I/O port UPS 3 I/O port External charger port UPS 4 I/O port 10A output socket (4 row) Figure 21 Rear panel of the 3-phase input single-phase output 3 + 1 POD iTrust Adapt 6kVA UPS User Manual...
  • Page 44: Appendix 5 Optional Part List

    6kVA UPS 1 + 1 POD - {R5} UF-POD314U11 single-phase input single-phase output rack model 6kVA UPS 3 + 1 POD - {R5} Guide rail/rack DMBM6.200.020 LCD unit UH52SA1Z1 The optional parts has been installed and debugged before delivery. iTrust Adapt 6kVA UPS User Manual...

This manual is also suitable for:

Itrust adaptUha1r-0050Uha1r-0050l

Table of Contents