9.0
W
I
IRING
NSPECTION
1. Verify all power connections are tightened per the torque specifications in Table 3.
2. Verify all control wire terminations are tight.
3. Verify all power wires and connections have proper spacing between exposed surfaces, phase-to-
phase and phase-to-ground.
4. Verify that all control wires are run in steel conduit, separate from all power wiring.
Table 2
Power wiring terminals, factory supplied
UPS Module Rating
100-225kVA
Use 75°C copper wire. Select wire size based on the ampacities in Table 5 of this manual, a reprint of
Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
Use commercially available solderless lugs for the wire size required for your application. Refer to
Table 3. Connect wire to the lug using tools and procedures specified by the lug manufacturer.
Table 3
Torque specifications
NUT AND BOLT COMBINATIONS
Bolt Shaft Size
1/4
5/16
3/8
1/2
CIRCUIT BREAKERS WITH COMPRESSION LUGS (FOR POWER WIRING)
Wire Size or Range
#6 - #4
#3 - #1
1/0 - 2/0
3/0 - 200 MCM
250 - 400 MCM
500 - 700 MCM
CIRCUIT BREAKERS WITH COMPRESSION LUGS (FOR POWER WIRING)
Current Rating
400 - 1200 Amps
TERMINAL BLOCK COMPRESSION LUGS (FOR CONTROL WIRING)
AWG Wire Size or Range
#22 -#14
NOTE: Use the values in this table unless the equipment is labeled with a different torque value.
For "SpaceSaver" modules in the 48" frame, rectifier and bypass input wiring is top-entry,
directly to lugs on top of their respective circuit breakers. DC link and critical bus output
connection are top-entry, to frame-mounted lugs.
Standard modules with top-and-bottom entry have access plates and a wireway on the
right side of the modules. All power connections are to busbars in the wireway.
Grade 2 Standard
Lb-in
53
107
192
428
Lb-in
100
125
150
200
250
300
Lb-in
300.00
Lb-in
3.5 to 5.3
27
Connection Type
Electrical Connections
with Belleville Washers
N-m
Lb-in
6.0
46
12
60
22
95
22
256
N-m
11
14
17
23
28
34
N-m
34.00
N-m
0.4 to 0.6

Wiring Inspection

N-m
5.2
6.8
11
29
DISCONTINUED
PRODUCT