Model Rating, VA (W)
Dimensions, in. (mm)
Shipping, W x D x H
Weight, lb (kg)
Input AC Parameters
Nominal Operating Frequency
Factory Default VAC
User-Configurable VAC
Operating Voltage Range
Without Battery Operation
Maximum Allowable VAC
Without Battery Operation
Input Power Connection
Output AC Parameters
Factory Default, VAC
Output Connections
Main Mode Overload
Battery Parameters
Recharge Time (Internal Batteries)
Bypass Protection Limits
Maximum Bypass Current
Disable Bypass Operation
Re-Enable Bypass Operation
Disable Bypass Operation
Environmental
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)
Transportation, °F (°C)
Operating Elevation
Agency
®
GXT3

specifications

Unit, W x D x H
Unit
Shipping
Input Frequency
Frequency
Waveform
>200% for 5 cycles; 151 - 200% for 1 second; 131-150% 10 seconds;
Type
Quantity x V
Battery Mfr. / Part #
Backup Time
Relative Humidity
Audible Noise
<55 dBA at 3.3ft (1m) from rear; <50 dBA at 3.3ft (1m) from front or sides
Safety
RFI/EMI
Surge Immunity
Transportation
10,000 (9000)
31.5 x 11.81 x 26.57 (800 x 300 x 675)
41.8 x 16.7 x 34 (1062 x 426 x 866)
308 (140)
428 (194)
50 or 60Hz (Factory Default = 60)
120/208 at 120 degrees
120 / 208 / 220 / 240
100 - 185 ±5VAC
40 - 70Hz
BYP, L1, L2, GND
Hardwire Terminal Block
Output: (GEC, X1, X2, X3, X4, GND) Bypass: L1, L2, GND
50Hz or 60Hz, Nominal
Sinewave
105 - 130% 1 minute
Valve-regulated, non-spillable, lead acid
20 x 12V
CSB HR1234R or Panasonic UP-RW1245
See Table 11
3 hr. to 90% capacity after full discharge into 100% load
If input voltage exceeds ±10% of the nominal voltage
If input voltage returns to within ±8% of nominal output voltage
When the input frequency prevents synchronous operation
32 to 86 (0 to 30) with 0.9 pf
86 to 104 (30 to 40) with 0.8pf
5 to 122 (-15 to 50)
0-95% non-condensing
Up to 3281 ft (1000m) at 80°F (27°C) without derating
UL 1778, c-UL
FCC Part 15, Subpart B, Class A
IEC/EN 61000-4-5, ANSI C62.41 (for North America)
ISTA Procedure 1B