Specifications - Emerson SolaHD S4K2U-5C Series User Manual

Industrial on-line ups 230 v, 1000 va–3000 va
Table of Contents

Advertisement

42 | 9.0 Specifications

9.0 Specifications
Table 11: UPS Specifications
Parameters
DIMENSIONS, D x W x H
Unit
Shipping
WEIGHT
Unit
Shipping
INPUT AC PARAMETERS
Voltage range
90% to 100% Loading
70% to 90% Loading
30% to 70% Loading
0% to 30% Loading
Power factor
Frequency
Input power receptacle
OUTPUT AC PARAMETERS
Output receptacles
Voltage
Frequency
Waveform
Overload
Power factor
BATTERy
Type
Qty x V x Rating
Battery mfr./Part number
Backup time
Recharge time
ENVIRONMENTAl REqUIREMENTS
Operating temperature
Storage temperatures
Relative humidity
S4K2U1000-5C
497 x 430 x 85 mm [19.6 x 16.9 x 3.3 in.]
717 x 570 x 262 mm [28.2 x 22.4 x 10.3 in.]
16.8 kg [37.0 lb.]
20.0 kg [44.1 lb.]
230 VAC nominal; variable based on output load
177 VAC/280 VAC
168 VAC/280 VAC
150 VAC/280 VAC
115 VAC/280 VAC
iEC 320 C14
iEC 320 C13 x 6
200/208/220/230/240 VAC (user-configurable) ±3%
200% for 2 seconds; 150%
for 1 minute with transfer to
bypass
4 x 12 V x 5.0 Ah
CSB/Hr1221W
3 hours to 90% capacity after full discharge with 100% load until UPS auto shutdown (internal batteries only)
0°C to +40°C [+32°F to +104°F]; see Table 13 for operating temperature parameters
Model
S4K2U2000-5C
23.2 kg [51.1 lb.]
26.0 kg [57.3 lb.]
0.99
40 Hz to 70 Hz; auto sensing
iEC 320 C20
50 Hz or 60 Hz
Sine wave
200% for 2 seconds; 150% for
50 seconds with transfer to
bypass
0.90
Valve-regulated, non-spillable, lead acid
4 x 12 V x 9.0 Ah
CSB/UPS12460
See Table 14
-15°C to +50°C [+5°F to +122°F]
0% to 95%, non-condensing
S4K2U3000-5C
602 x 430 x 85 mm [23.7 x 16.9 x 3.3 in.]
717 x 570 x 262 mm [28.2 x 22.4 x 10.3 in.]
32.4 kg [71.4 lb.]
36.0 kg [79.4 lb.]
196 VAC/280 VAC
184 VAC/280 VAC
161 VAC/280 VAC
115 VAC/280 VAC
iEC 320 C13 x 6; iEC 320 C19 x 1
200% for 2 seconds; 150% for 55 seconds
with transfer to bypass
6 x 12 V x 9.0 Ah

Advertisement

Table of Contents
loading

Table of Contents