RADION receiver SD
RADION smoke
For UL installations THIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE THAT WILL
RESULT IN A DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS. THE
TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60
SECONDS. NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS
UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
RADION contact SM
During the installation of the device, UL installations primary securement means shall be
screws.
RADION contact RM
During the installation of the device, UL installations primary securement means shall be
screws.
RADION specialty
When programming the bill trap, special programming for a hold up device is required.
Program the point as follows:
For UL installations, the RFBT-A shall be permanently mounted using the 3M VHB 4956 double
sided adhesive tape. The suitable surfaces are:
RADION universal transmitter
During the installation of the device, the following items are required by UL:
Bosch Security Systems, Inc.
P## Type = 2 (Point is constantly armed regardless of the status of the system).
ᅳP## Invisible Point = Yes (Keypads do not display alarm activity from this point).
Aluminum
Galvanized steel
Stainless steel
Enameled steel
Nickel Coated ABS
Glass (with or without Silane Coating
PVC
Glass/Epoxy
PBT
Polycarbonate
Acrylic/Polyurethane paint
Polyester paint
For UL installations, an UL Listed burglar alarm dry contact device shall be connected if
the external terminal is used.
When external contact is configured for UL hold up installations, a hold up device such as
potter electric model HUB is to be connected to the external contact. For programming,
refer to the appropriate control panel manual "Special programming required for a hold
up device." Point shall be programmed as stated below:
P## Type = 1 Instant on open or short (Point is constantly armed regardless of the
status of the system).
ᅳP## Invisible Point/Silent Bell = Yes (Keypads do not display alarm activity from this
point).