IMPORTANT NOTE ON
VOLTAGE DROP CALCULATIONS
The ElectriCalc Pro calculates voltage
drop and wire size using DC resistance
as defined by the 2002 NEC. To find
the voltage drop for a specific wire size,
you must first enter amps and the one-
way wire length (and other required
variables), entering the specific wire
size last . Otherwise, for your safety the
calculator will recalculate the wire sizes
based on the '99 NEC Ampacity Tables
and maximum allowable voltage drop.
Finding Single-Phase
Voltage Drop
You are installing 175 feet of 75°C, #8
THW branch circuit copper conductors
to supply an 11A load on a 208V 1Ø
system. What is the source voltage
drop at the load?
Steps
Reset calculator
Set to 1-phase
Set to 75°C
Enter amps
Enter volts
Enter length
Enter wire size
Solve volt. drop
Solve % v.drop
Keystrokes
[Set] [x] [On/C]
[Set] [1]
[Set] [7]
11 [Amps]
208 [Volts]
175 [Length]
8 [WireSz]
[VD%]
[VD%]
User's Guide — 43
Display
1Ø 75 Cu 1 PH
11. AMPS
208. VOLT
175. FEET
AWG WIRE SIZE
3.0 DROP V
1.4 DROP V %
0.
1 PH