Dimplex SOLCU Installation And Operating Instructions Manual page 71

Temperature difference controller 5 inputs, 2 outputs
Table of Contents

Advertisement

Solid fuel boiler:
Factory
Adjustable
setting
down to
min.
Temperature controlled:
Switch-on temperature difference:
6 K
Switch-off
temperature
difference
+ K
Switch-off temperature difference:
3 K
0 K
Maximum heat target temperature:
60 °C
0 °C
Minimum heat source temperature:
50 °C
30 °C
Quick charge:
Factory
Adjustable
setting
down to min.
Temperature controlled:
Switch-on temperature:
50 °C
0 °C
Switch-off temperature:
5 °C
Switch-on tem-
perature + K
EN
Adjustable
Comment
up to max.
0 K
Switch-on
temperature
difference - K
150 °C
95 °C
Adjustable
Comment
up to max.
95 °C
The switch-off temperature is adjusted according
to the hysteresis.
Switch-on
temperature +
10 K
730.138 | 08.1
71

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solcu2

Table of Contents