The solar pump operates, despite the fact that the switch-on condition is not
fulfilled:
Secondary symptoms
The pump symbol in
the display rotates
•
Symbol rotates
•
Display has a red
background
•
Tool symbol is visible
on the display
Solar pump is operating, activation condition is fulfilled, nevertheless, no heat
transport in the solar circuit (no "fluid circulation"):
Secondary symptoms
The pump symbol in
the display rotates
Solar pump shows cycle behaviour
Secondary symptoms
10.2
Pt1000 temperature sensor values
A potentially defective sensor can be checked using an ohmmeter To do this, the sensor must be discon-
nected, its resistance measured, and the value compared with the figures in the table below. Small devia-
tions are acceptable.
Temperature [°C]
Resistance [Ω]
Temperature [°C]
Resistance [Ω]
60
Possible cause
•
The interval function is acti-
vated
•
The holiday function is acti-
vated
•
The frost protection function is
activated
•
Blockage protection is acti-
vated
The operating switch is set to
manual operation and the pump
output is set to "on"
Possible cause
•
Air is in the solar circuit
•
The isolating valve is closed
•
Limescale/contamination on
solar circuit
Possible cause
•
Temperature difference too
small
•
Collector sensor incorrectly
positioned
-30
-0
-10
88
9
961
80
90
100
1309 1347 1385 143 1461 1498 1536 1573 1611 1648 1685
EN
Procedure
•
No fault
•
Deactivate the relevant function, if
necessary
•
Set the operating switch to auto-
matic operation
Procedure
•
Check the solar circuit for air
•
Check the isolating valve
•
Flush/clean the solar circuit
Procedure
•
Adjust temperature difference in the
Parameters menu
•
Check the collector sensor
0
10
0
1000 1039 1078 1117 1155 1194 13 171
110
10
130
730.138 | 08.1
30
40
50
140
150
160
60
70
170
180