Parameter Settings - Dimplex SOLCU Installation And Operating Instructions Manual

Temperature difference controller 5 inputs, 2 outputs
Table of Contents

Advertisement

13.2

Parameter settings

Maximum temperature storage tank 1 and storage tank 2:
Factory
Adjustable
setting
down to
min.
60 °C
0 °C
Maximum pool temperature:
Factory
Adjustable
setting
down to
min.
30 °C
10 °C
Switch-on temperature difference solar 1 and solar 2:
Factory
Adjustable
setting
down to
min.
8 K
Switch-off
temperature
difference
+ K
Switch-off temperature difference solar 1 and solar 2:
Factory
Adjustable
setting
down to
min.
4 K
0 K
Switch-on temperature difference external heat exchanger:
Factory
Adjustable
setting
down to
min.
6 K
EN
Adjustable
up to max.
95 °C
Adjustable
up to max.
45 °C
Adjustable
up to max.
50 K
Adjustable
up to max.
Switch-on
temperature dif-
ference - K
Adjustable
up to max.
-
-
730.138 | 08.1
Description
When the maximum temperature of storage tank 1
(storage tank ) is reached, storage tank 1 (storage
tank ) is not loaded until the temperature drops to
3 K below the defined maximum value.
Description
When the maximum pool temperature is reached,
the swimming pool is not loaded until the tempera-
ture drops to 3 K below the defined maximum value.
Description
When the switch-on temperature difference be-
tween collector and storage tank is reached, the
storage tank is loaded.
Description
When the switch-off temperature difference
between collector and storage tank is reached, load-
ing of the storage tank is stopped. The difference
between the switch-on temperature difference and
the switch-off temperature difference must be at
least  K, and is barred from being set any lower.
Description
When the switch-on temperature difference
between the secondary side of the external heat
exchanger and the storage tank is reached, the stor-
age tank is loaded. This value cannot be changed.
67