Modes of operation

6.1

"OFF" mode

In order to switch off the outputs, slide the operating switch down.
A new window appears in the display, which shows "OFF", as
well as the controller software version number and the number
of the chosen system. The display is backlit in red.
In "OFF" mode, all outputs (R1, R) are switched off.
NOTE
On delivery from the manufacturer, the switch is set to "OFF".
6.2

"Automatic" mode

CAUTION
Damage to pump caused by dry operation!
The controller may only be set to "Automatic" when the system has been
filled.
In order to switch the outputs to "Automatic", slide the operating
switch to the middle position.
The status appears in the display.
This mode of operation is the automatic controller mode and must be
set for automatic operation.
NOTE
During normal system operation, the operating switch should always
be set to "Automatic".
6.3

"Manual" mode

CAUTION
Damage to pump caused by dry operation!
The controller may only be set to "Manual" when the system has been
filled.
When operating the device for the first time, or when testing the func-
tion, the controller outputs can be manually switched.
In order to switch the outputs manually, slide the operating switch up.
The display is backlit in red and a settings window is displayed.
: choose the desired output.
SET: switch the selected output to "on" or "off".
ESC: close the settings window.
The current recorded values can now also be queried for the
purpose of checking.
: access measured values.
SET: reopen the settings window.