7.3.8
Difference thermostat function
This function allows a controller output to be controlled depending on
a pre-defined temperature difference.
When the temperature difference exceeds the defined "on" value, the
output is switched on until the temperature difference falls below the
"off" value. For optimised functionality, unloading of the heat source can
be limited to a particular temperature range, and loading of the heat
target can be limited to a maximum value.
It is also possible to limit the difference thermostat function to specific
times.
Defining the inputs and the switching values
"Functions" submenu selected, see "Selecting a function"
(see chapter 7.3.1).
Difference thermostat activated, see "Activating a function"
(see chapter 7.3.1).
Outputs selected, see "Selecting an output" (see chapter 7.3.1).
: press button.
The display for setting the temperature inputs and the switching
values appears.
SET: press button.
"T" flashes in the display (temperature input for the heat source).
: choose the (heat source's) input.
SET: press button to confirm.
"T" flashes in the display (temperature input for the heat target).
: choose the (heat source's) input.
SET: press button to confirm.
The "on" value flashes after confirmation of the heat target input.
: set the "on" value.
SET: press button to confirm.
The "off" value flashes after confirmation of the "on" value.
: set the "off" value.
SET: press button to confirm.
The settings are saved.
Defining limits for the heat source
: press button.
The display for setting the limits (max, min) of the heat source
appears.
SET: press button.
"max" flashes in the display (heat source's maximum value).
: set the maximum value.
SET: press button to confirm.
"min" (heat source's minimum value) flashes after
confirmation of the maximum value.
: set the minimum value.
SET: press button to confirm.
The settings are saved.
46
EN
 
[......................]
[......................]
Display: 3.7
Display: 3.7
[Difference thermostat]
[Difference thermostat]
 
Display: 3.7.3
Display: 3.7.3
[on]
[on]
[off]
[off]
 
Display: 3.7.4
Display: 3.7.4
730.138 | 08.1
T
T
?
?
T
T
?
?
[...]: 6 K
[...]: 6 K
[...]: 3 K
[...]: 3 K

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solcu2

Table of Contents