Insert Placement Requirements; Hearth Requirements; Insert Size Requirements - Lopi Freedom Owner's Manual

Masonry fireplace insert
Table of Contents

Advertisement

I
P
NSERT
LACEMENT
¥
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the insert
¥
Insert and hearth must be installed on a level, secure floor
¥
The clearances listed below must be met:
Measure all side
and top clearances
from this top plate
l e
t i b
u s
m b
a l l
C o
e w
S i d
H
R
EARTH
EQUIREMENTS (See the illustration above)
¥
Must extend 16" in front of the insert and 8" on both sides (45 1/4" wide by 23" deep, 17 5/8"
deep with flush kit)
¥
Must be non-combustible and at least .018" thick (26 gage)
I
S
R
NSERT
IZE
EQUIREMENTS
R
EQUIREMENTS (See the illustration below)
Surround
Panels
A
B
F
B
A
E
D
C
F
I
I
NSERT
NSTALLATION
Combustible Mantle
D
C
E
(C
ONT
Minimum
Extended
Clearances
(standard)
A Sidewall to Insert
15"
B Side Facing
13 1/2"
C Top Facing
30"
With mantle shield
17"
D Mantle to Insert
32"
With mantle shield
19"
E Hearth (Front)*
16"
F Hearth (Side)**
8"
* Does not include the
distance the insert sticks
out on the hearth (7",
1 5/8" if using the flush kit).
**Total hearth width must be
at least 45 1/4"
Minimum Masonry
Fireplace Size
A Height* (front)
21 3/4"
B Height* (rear)
21 3/4"
C Width (front)
29 1/4"
D Width (rear)
21 1/4"
E Depth
13 1/2"
F Hearth**
7"
* Older model panels may use the
heightened yoke, adding 7/8" to the
height. Furthermore, additional height is
needed to align the pipe on positive and
direct connect installations.
** Does not include the required 16" of
floor protection in front.
.)
P
7
AGE
With
Flush Kit
15"
13 1/2"
20"
N/A
20"
N/A
16"
8"
With
Flush Kit
21 3/4"
21 3/4"
29 1/4"
21 1/4"
18 7/8"
1 5/8"