Insert Placement Requirements
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" (915mm) of the front of the insert
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements in Figure 3 must be met.
Minimum Clearances
a Mantel
(combustible)
with Mantel Shield
b Top Facing
(non-combustible)
with Mantel Shield
c Side Facing
(non-combustible)
d Sidewall
Masonry Fireplace Requirements
Chimney must have a clay tile liner or a stainless steel liner (positive connection)
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired
prior to installation of the insert
Chimney height: 15' (4.5M) minimum; 33' (10M) maximum (measured from the base of the insert).
Entire fireplace, including chimney, must meet local building requirements
Drafting Performance
This appliance relies upon natural draft to operate. External forces, such as wind, barometric pressure,
topography, or factors of the home (negative pressure from exhaust fans, chimneys, air infiltration, etc.),
may adversely affect draft. Travis Industries cannot be responsible for external forces leading to less
than optimal performance.
© Travis Industries
Installation
(for qualified installers only)
Masonry Fireplace
32" 813mm
- - - - - - - - - - - - - - -
19" 483mm
30" 762mm
- - - - - - - - - - - - - - -
17" 432mm
13.5" 343mm
15" 381mm
100-01279
9
Figure 3
4111102